Skip to main content
Siemens 3VA1116-1AA32-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA32-0BA0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA32-0BA0

Siemens SENTRON 3VA1116-1AA32-0BA0, switch disconnector in MCCB design, 3-pole, 160 A, 690 V AC, with undervoltage release 24 V DC, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA32-0BA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1116-1AA32-0BA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Power loss, max.38 W
3VA1116-1AA32-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA32-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1116-1AA32-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA32-0BA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1116-1AA32-0BA0 is a 3-pole switch disconnector in a molded-case circuit breaker (MCCB) footprint, rated 160 A continuous at 40 °C through 50 °C. It provides visible isolation and safe disconnection under load — no overload or short-circuit protection built in, so it's strictly a disconnect, not a breaker. The undervoltage release (UVR) set for 24 V DC will trip the switch open if control voltage drops, which is common in emergency-stop chains or safety circuits where loss of power must open the load.

That covers most 400 V and 480 V industrial distribution systems with headroom. Maximum power loss is 38 W, which is modest for this current class and won't drive much additional heat inside a ventilated cabinet.

It's a front-terminal, busbar-connection design — the main circuit wires land on the front face, not the back. That's typical for MCCB-style disconnectors in panelboard or switchboard layouts. No auxiliary contacts are included, and there's no communication function — it's a pure disconnect with UVR. If you need aux contacts for status feedback, you'll add them externally.

Frequently asked questions

Does 3VA1116-1AA32-0BA0 drop into a panel designed for 3VA1112-5EF32-0CA0?

Physically yes — same 70 mm depth, 76.2 mm width, 130 mm height, and both use front-terminal busbar connections. The difference is function: the 3VA1116-1AA32-0BA0 is a switch disconnector with no overcurrent protection, while the 3VA1112-5EF32-0CA0 is a molded-case circuit breaker with a TM240 trip unit. If the panel relies on the breaker for protection, swapping in the disconnect requires adding upstream overcurrent protection.

MPN