Skip to main content
Siemens 3VA1116-1AA32-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA32-0HH0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA32-0HH0

Siemens SENTRON 3VA1 switch disconnector, IEC frame 160, 3-pole, In=160 A, without overload or short-circuit protection, with shunt trip STL 12-30 V DC / 24 V AC, 2 auxiliary switches HQ + 1 trip alarm switch HQ, busbar connection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA32-0HH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1116-1AA32-0HH0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1116-1AA32-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA32-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1116-1AA32-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA32-0HH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1116-1AA32-0HH0 is a SENTRON 3VA1 switch disconnector in MCCB design, rated for 160 A continuous current (Iu) across 3 poles. It is built for isolation and switching duty without integral overload or short-circuit protection — the protection function is handled upstream or by a separate release. Busbar connection on the front terminals keeps panel wiring clean for high-current feeds.

The 160 A rated continuous current (Iu) determines the maximum load this disconnector can carry continuously without exceeding its thermal limits. For motor or resistive loads at that current, the 38 W maximum power loss must be dissipated within the enclosure — factor that into panel thermal calculations. The rated insulation voltage of 800 V and max operational voltage of 690 V AC 50/60 Hz or 500 V DC cover standard 400/480 VAC industrial supplies and many DC bus applications, but the DC rating is the limiting factor for battery or drive-link circuits.

This 3-pole disconnector mounts in a panel or enclosure on a DIN rail or direct-mount plate — the 76.2 mm width, 70 mm depth, and 130 mm height fit standard 3VA1 frame spacing. Front terminals with busbar connection mean the main power path is a bolted bus link, not lugged wire; plan for busbar drop-in rather than individual cable terminations. IP40 on the front is splash-protected but not washdown-rated — keep it behind a sealed enclosure door in wet environments.

Operating limits and endurance

The shunt trip coil (STL) on this variant triggers on a separate control signal; there is no undervoltage release or communication function built in.

Frequently asked questions

Where can I buy the 3VA1116-1AA32-0HH0?

The part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

Will the 3VA1116-1AA32-0HH0 drop into a panel specified for 3VA1110-5EE32-0JA0 without rewiring?

The dimensions are identical (same width, depth, height), and both use front terminal connections. However, the 3VA1116-1AA32-0HH0 uses busbar connection on the main circuit, while the 3VA1110-5EE32-0JA0 uses lug terminals — verify the busbar interface matches your existing panel layout before swapping.

What compliance documentation is available for this part?

The evidence does not list specific compliance certifications (UL, CSA, CE, RoHS, REACH) for this order code. As a Siemens SENTRON product, it is designed to meet IEC standards for switch disconnectors, but exact documentation should be confirmed at quote time.

MPN
3VA1116-1AA32-0HH0