Skip to main content
Siemens 3VA1116-1AA32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA32-0JA0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA32-0JA0

Siemens SENTRON 3VA1116-1AA32-0JA0, switch disconnector in MCCB design, 3-pole, 160 A rated continuous current, IP40 front, with integrated shunt trip (STL) 110-127 V DC/AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1116-1AA32-0JA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1116-1AA32-0JA0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1116-1AA32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1116-1AA32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA32-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1116-1AA32-0JA0 is a SENTRON switch disconnector in a 3VA IEC frame 160, 3-pole, rated 160 A continuous current (Iu). It is explicitly designed without overload or short-circuit protection — this is a disconnect-only device, not a molded case circuit breaker. The MCCB design form factor means it occupies the same panel footprint as a 3VA breaker, but the internal construction is a simple switch mechanism rated for isolation duty. Rated insulation voltage Ui is 800 V, with maximum operational voltage 690 V AC 50/60 Hz and 500 V DC. The shunt trip release (STL) is factory-fitted for 110-127 V DC/AC, enabling remote tripping.

Dimensions are 76.2 mm wide, 130 mm high, 70 mm deep — the same 3-pole width as a 3VA breaker in the 160 A frame. Main circuit connection is via busbar connection with front terminals; this is a fixed-front disconnect, not a plug-in unit. The busbar connection style means it's designed for a common busbar system within the panel, not for individual cable lugs on the line side. The wide storage range matters for spares held in unheated warehouses. The optional motor drive (product extension available) allows remote motorized operation if needed later.

Frequently asked questions

What is the closest functional alternative to 3VA1116-1AA32-0JA0?

The closest functional peer in the same 3VA frame is 3VA1110-5EE32-0JA0, which is a molded case circuit breaker (line protection) rated 100 A with a TM220 overcurrent release. That part provides overload and short-circuit protection that this switch disconnector deliberately omits. The 3VA1116-1AA32-0JA0 is a disconnect-only device — if your circuit requires protection, you need the breaker variant.

Will 3VA1116-1AA32-0JA0 drop into a panel specified around 3VA1110-5EE32-0JA0 without rewiring?

The dimensions are identical (76.2 mm wide, 130 mm high, 70 mm deep) and both use the same 3VA frame 160 footprint. However, the 3VA1116-1AA32-0JA0 uses busbar connection for the main circuit, while the 3VA1110-5EE32-0JA0 uses lug terminals. Verify your panel's busbar system compatibility — the connection method differs.

MPN
3VA1116-1AA32-0JA0