Skip to main content
Siemens 3VA1116-1AA32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA32-0JH0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA32-0JH0

Siemens SENTRON 3VA1 IEC frame 160, switch disconnector 3VA1116-1AA32-0JH0, 3-pole SD100, 160 A rated continuous current, busbar connection, shunt trip (STL) 110-127 V DC/AC, 2 auxiliary switches HQ + 1 trip alarm switch HQ, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA32-0JH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1116-1AA32-0JH0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1116-1AA32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1116-1AA32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA32-0JH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

It carries no overload or short-circuit release; its job is to provide a visible-break disconnect point in a distribution or motor feeder circuit, with a shunt trip (STL) coil rated 110–127 V DC/AC for remote or emergency-off tripping. Rated insulation voltage Ui is 800 V, max operational voltage 690 V AC 50/60 Hz and 500 V DC. That puts it comfortably inside standard 400/480 VAC industrial panels and most 500 VDC battery or converter circuits. The front terminal busbar connection means it lands directly on a busbar stack — no lug terminals on the line side — so panel layout needs to account for that busbar interface rather than individual cable entry. That gives three independent signal paths — two for status feedback (open/closed) and one dedicated to trip indication. The trip alarm switch changes state only when the shunt trip or a manual trip event operates the mechanism, so a PLC or annunciator gets a clean, latched signal that a fault trip occurred.

The 3VA1 frame measures 70 mm deep, 76.2 mm wide, 130 mm tall — a standard MCCB footprint that fits a 3-pole slot in a SENTRON distribution panel or a DIN-rail adapter plate. The busbar connection on the main circuit uses a front-terminal arrangement, so busbar runs need to terminate at the front face of the breaker — not at the rear or side. Maximum power loss is 38 W at rated current. That is the heat the disconnect dissipates in a closed, loaded state — relevant for enclosure thermal calculations, especially in a sealed or high-ambient cabinet. The mechanical endurance is 15,000 operating cycles, which is typical for a switch disconnector in this frame size — adequate for daily switching in a production line, not for continuous high-cycle duty.

Frequently asked questions

How do I get current pricing and availability for 3VA1116-1AA32-0JH0?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; availability and current pricing are confirmed at quote time.

What is the difference between 3VA1116-1AA32-0JH0 and 3VA1110-5EE32-0JA0?

The 3VA1110-5EE32-0JA0 is a molded case circuit breaker with a TM220 thermal-magnetic release (overload and short-circuit protection), while the 3VA1116-1AA32-0JH0 is a switch disconnector with no overcurrent protection. The 3VA1116 carries a higher 160 A continuous rating vs 100 A on the breaker, and includes factory-fitted auxiliary switches (2 CO + 1 trip alarm) that the breaker lacks. Both share the same 3VA1 frame dimensions (70 x 76.2 x 130 mm) and 3-pole busbar connection, so the disconnector can drop into the same panel slot — but the circuit breaker provides protection and the disconn

What are the key ratings of the 3VA1116-1AA32-0JH0?

Rated continuous current Iu = 160 A, rated insulation voltage Ui = 800 V, max operational voltage 690 V AC 50/60 Hz and 500 V DC. Shunt trip coil rated 110–127 V DC/AC. 3 poles, IP40 front, busbar connection, 2 auxiliary switches + 1 trip alarm switch.

MPN
3VA1116-1AA32-0JH0