Skip to main content
Siemens 3VA1116-1AA36-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA36-0AC0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA36-0AC0

Siemens SENTRON 3VA1 IEC frame 160, switch disconnector, 3-pole, In=160 A, without overload or short-circuit protection, front terminal connection, 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-1AA36-0AC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1116-1AA36-0AC0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W

Construction & Connection

3VA1116-1AA36-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-1AA36-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1116-1AA36-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-1AA36-0AC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this part is — and isn't

The Siemens 3VA1116-1AA36-0AC0 is a SENTRON switch disconnector in a 3VA1 molded-case frame, rated 160 A continuous current (Iu) across 3 poles. It is not a circuit breaker — no overload or short-circuit release inside. It provides visible isolation for a load circuit, with a 15 000-cycle mechanical endurance. Front terminal connection, 70 mm deep, 76.2 mm wide, 130 mm tall, IP40 on the front face. Rated for AC 690 V (50/60 Hz) and DC 500 V maximum operational voltage. The 2 kA limited short-time rating (1 s and 0.5 s) confirms it is built for isolation duty, not fault interruption — upstream protection handles the clearing.

Panel fit and integration

Same 76.2 mm wide footprint as the 3VA1 MCCB line — drops into the same DIN-rail or panel-mount cutout. Two HQ auxiliary switches (CO contacts) come fitted; no undervoltage release, no communication module, no voltage-trip accessory. Optional motor drive can be added later via the product extension slot. Operating temperature range -25 °C to +70 °C; storage from -40 °C to +80 °C. Maximum power dissipation 38 W at full rated current — factor that into enclosure thermal rise calculations.

Frequently asked questions

Where can I buy 3VA1116-1AA36-0AC0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

Will this drop into a panel built for 3VA1110-5ED36-0AC0?

Yes — same 76.2 mm width, 70 mm depth, 130 mm height, and front-terminal connection. The 3VA1116-1AA36-0AC0 is a switch disconnector (no overcurrent protection), while the 3VA1110-5ED36-0AC0 is a molded-case circuit breaker with a TM210 release. Mechanical fit is identical; wiring and bus-bar positions match.

MPN
3VA1116-1AA36-0AC0