Siemens 3VA1116-1AA36-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA36-0AG0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA36-0AG0

Siemens SENTRON 3VA1116-1AA36-0AG0, switch disconnector in MCCB design, 3-pole, In=160 A, SD100, without overload or short-circuit protection, front terminal connection, 1 auxiliary switch HP + 1 trip alarm switch HP.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-1AA36-0AG0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON

Ratings

3VA1116-1AA36-0AG0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Power loss, max.38 W

Construction & Connection

3VA1116-1AA36-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-1AA36-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1116-1AA36-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-1AA36-0AG0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What it is and what it does

The Siemens 3VA1116-1AA36-0AG0 is a SENTRON 3-pole switch disconnector in a molded-case circuit breaker (MCCB) physical design, rated 160 A continuous at 40 °C through 50 °C. It provides no overload or short-circuit protection — it is a straight disconnect for isolation and switching duty, not a protective device. The front terminal connection accepts standard lug or clamp terminations for the main circuit.

Thermal performance and derating

Rated 160 A from 40 °C to 50 °C ambient. Above 50 °C the current must be derated: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. The operating ambient range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. Maximum power dissipation is 38 W at rated load.

Voltage ratings and auxiliary configuration

Rated insulation voltage 800 V, operating voltage 690 V AC and 500 V DC. The unit ships with one auxiliary switch and one trip alarm switch (HP type), providing two CO contacts for auxiliary signaling. No undervoltage release, no voltage trigger, no communication function. Mechanical service life is 15,000 operating cycles typical.

Panel fit and protection

Dimensions: 130 mm height, 76.2 mm width, 70 mm depth. Front face is IP40 rated. The MCCB-style footprint matches standard 3VA100/3VA110 cutouts and busbar systems. Optional motor drive available for remote operation.

Frequently asked questions

What are the key ratings for this switch disconnector?

Rated 160 A continuous from 40 °C to 50 °C, with derating above that. Insulation voltage 800 V, operating voltage 690 V AC / 500 V DC. Three poles, front terminal connection, IP40 front protection.

Where can I buy the 3VA1116-1AA36-0AG0?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

Will the 3VA1116-1AA36-0AG0 fit in a panel designed for a 3VA1110-5EF32-0AM0?

Yes. Both share the same MCCB footprint: 130 mm height, 76.2 mm width, 70 mm depth. The 3VA1116-1AA36-0AG0 is a switch disconnector without overcurrent protection, while the peer is a molded case circuit breaker with a TM240 release. Panel cutout and busbar connections are identical, so no rewiring is needed for the disconnect function.

MPN
3VA1116-1AA36-0AG0