Skip to main content
Siemens 3VA1116-1AA36-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA36-0AG0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA36-0AG0

Siemens SENTRON 3VA1116-1AA36-0AG0, switch disconnector in MCCB design, 3-pole, In=160 A, SD100, without overload or short-circuit protection, front terminal connection, 1 auxiliary switch HP + 1 trip alarm switch HP.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA36-0AG0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1116-1AA36-0AG0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Power loss, max.38 W
3VA1116-1AA36-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA36-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts2
3VA1116-1AA36-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA36-0AG0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1116-1AA36-0AG0 is a SENTRON 3-pole switch disconnector in a molded-case circuit breaker (MCCB) physical design, rated 160 A continuous at 40 °C through 50 °C. It provides no overload or short-circuit protection — it is a straight disconnect for isolation and switching duty, not a protective device. The front terminal connection accepts standard lug or clamp terminations for the main circuit.

Thermal performance and derating

Above 50 °C the current must be derated: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. Maximum power dissipation is 38 W at rated load.

Voltage ratings and auxiliary configuration

Rated insulation voltage 800 V, operating voltage 690 V AC and 500 V DC. Mechanical service life is 15,000 operating cycles typical.

Panel fit and protection

Front face is IP40 rated. The MCCB-style footprint matches standard 3VA100/3VA110 cutouts and busbar systems. Optional motor drive available for remote operation.

Frequently asked questions

What are the key ratings for this switch disconnector?

Rated 160 A continuous from 40 °C to 50 °C, with derating above that. Insulation voltage 800 V, operating voltage 690 V AC / 500 V DC. Three poles, front terminal connection, IP40 front protection.

Where can I buy the 3VA1116-1AA36-0AG0?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

Will the 3VA1116-1AA36-0AG0 fit in a panel designed for a 3VA1110-5EF32-0AM0?

Yes. Both share the same MCCB footprint: 130 mm height, 76.2 mm width, 70 mm depth. The 3VA1116-1AA36-0AG0 is a switch disconnector without overcurrent protection, while the peer is a molded case circuit breaker with a TM240 release. Panel cutout and busbar connections are identical, so no rewiring is needed for the disconnect function.

MPN