Skip to main content
Siemens 3VA1116-1AA36-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA36-0CA0 Switch Disconnector, 160 A, 3-Pol

MPN3VA1116-1AA36-0CA0

Siemens SENTRON 3VA1 switch disconnector, IEC frame 160, 3-pole, In=160 A, without overload or short-circuit protection, clamp connection, undervoltage release (UVR) 120-127 V AC 50/60 Hz, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-1AA36-0CA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1116-1AA36-0CA0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W

Construction & Connection

3VA1116-1AA36-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-1AA36-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1116-1AA36-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-1AA36-0CA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1116-1AA36-0CA0 is a SENTRON 3VA1 switch disconnector in MCCB design, rated for 160 A continuous current (Iu) across a 3-pole configuration. It carries a rated insulation voltage of 800 V and a max AC operational voltage of 690 V (50/60 Hz), with a DC rating of 500 V. This unit ships without overload or short-circuit protection — it is a pure disconnecting means, not a circuit breaker — and includes an undervoltage release (UVR) coil rated 120–127 V AC.

What the 160 A rating means for your panel

At 160 A continuous, this switch disconnector handles the full load current of a moderately sized feeder or a large motor branch circuit. The 3-pole front-terminal connection (clamp type) accepts standard lug wiring — expect to land conductors sized for 160 A (typically 2/0 AWG copper at 75 °C termination). The IP40 front protection means the operator face is sealed against tools and small debris, but the enclosure itself must provide the overall panel IP rating. Dimensions are 70 mm deep, 76.2 mm wide, and 130 mm tall — a compact footprint that fits standard DIN-rail or panel-mount cutouts for the 3VA frame 160 family.

Frequently asked questions

Where can I buy 3VA1116-1AA36-0CA0?

This part is sourced and quoted to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time.

Will 3VA1116-1AA36-0CA0 drop into a panel specified around 3VA1112-5EF32-0CA0 without rewiring?

Yes, the physical footprint is identical: same depth (70 mm), width (76.2 mm), height (130 mm), and front-terminal arrangement. The wiring lugs and bus-bar positions are compatible. The main difference is that 3VA1116-1AA36-0CA0 lacks overcurrent protection — it is a switch disconnector, not a circuit breaker — so the panel's upstream protection must already be sized for the 160 A frame.

MPN
3VA1116-1AA36-0CA0