Skip to main content
Siemens 3VA1116-1AA36-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA36-0HH0 Switch Disconnector, 160 A, 3-Pol

MPN3VA1116-1AA36-0HH0

Siemens SENTRON 3VA1116-1AA36-0HH0, switch disconnector in MCCB design, 3-pole, 160 A, shunt trip release 12-30 V DC / 24 V AC, with 2 auxiliary switches and 1 trip alarm switch, front terminal connection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA36-0HH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1116-1AA36-0HH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Power loss, max.38 W
3VA1116-1AA36-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA36-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts3
3VA1116-1AA36-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA36-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1116-1AA36-0HH0 is a SENTRON switch disconnector built in an MCCB (molded case circuit breaker) form factor. It is rated for 160 A continuous at 40 °C through 50 °C, with a shallow derating curve: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. It has no overload or short-circuit protection — this is a pure disconnect, not a breaker. The built-in shunt trip release (STL) accepts 12–30 V DC or 24 V AC 50/60 Hz, so you can remote-trip it from an emergency stop circuit or a PLC digital output.

Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall — the standard 3VA frame size. Front terminal connections accept clamp-type wiring for the main circuit. Mechanical service life is 15 000 operating cycles typical, which covers most switching and isolation duty in distribution boards.

Frequently asked questions

Will 3VA1116-1AA36-0HH0 drop into a panel specified for 3VA1110-5EF32-0AM0?

The frame dimensions are identical — both share 70 mm depth, 76.2 mm width, and 130 mm height — so the mechanical footprint is a direct drop-in. The key difference is function: the 3VA1116-1AA36-0HH0 is a switch disconnector with a shunt trip, while the 3VA1110-5EF32-0AM0 is a molded case circuit breaker with thermal-magnetic overcurrent protection. If the panel design requires overcurrent protection, the disconnector alone will not fulfill that role.

Where can I buy 3VA1116-1AA36-0HH0?

This part is sourced to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN