Skip to main content
Siemens 3VA1116-1AA36-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA36-0HH0 Switch Disconnector, 160 A, 3-Pol

MPN3VA1116-1AA36-0HH0

Siemens SENTRON 3VA1116-1AA36-0HH0, switch disconnector in MCCB design, 3-pole, 160 A, shunt trip release 12-30 V DC / 24 V AC, with 2 auxiliary switches and 1 trip alarm switch, front terminal connection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-1AA36-0HH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON

Ratings

3VA1116-1AA36-0HH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Power loss, max.38 W

Construction & Connection

3VA1116-1AA36-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-1AA36-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1116-1AA36-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-1AA36-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What it is and what it does

The Siemens 3VA1116-1AA36-0HH0 is a SENTRON switch disconnector built in an MCCB (molded case circuit breaker) form factor. It is rated for 160 A continuous at 40 °C through 50 °C, with a shallow derating curve: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. This means in a warm enclosure you lose only about 6% of capacity at the top end — usable in most standard panels without oversizing. It has no overload or short-circuit protection — this is a pure disconnect, not a breaker. The built-in shunt trip release (STL) accepts 12–30 V DC or 24 V AC 50/60 Hz, so you can remote-trip it from an emergency stop circuit or a PLC digital output. Two auxiliary switches HQ plus one trip alarm switch HQ give status feedback for the panel controller.

Panel fit and wiring

Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall — the standard 3VA frame size. Front terminal connections accept clamp-type wiring for the main circuit. The IP40 front protection means it is suited for enclosed panel mounting where no water jets hit the face. Mechanical service life is 15 000 operating cycles typical, which covers most switching and isolation duty in distribution boards. Maximum power loss is 38 W at rated current — factor that into your enclosure thermal calculation if the panel is densely packed. Insulation voltage is rated 800 V, operating voltage 690 V AC or 500 V DC.

Frequently asked questions

Will 3VA1116-1AA36-0HH0 drop into a panel specified for 3VA1110-5EF32-0AM0?

The frame dimensions are identical — both share 70 mm depth, 76.2 mm width, and 130 mm height — so the mechanical footprint is a direct drop-in. The key difference is function: the 3VA1116-1AA36-0HH0 is a switch disconnector with a shunt trip, while the 3VA1110-5EF32-0AM0 is a molded case circuit breaker with thermal-magnetic overcurrent protection. If the panel design requires overcurrent protection, the disconnector alone will not fulfill that role.

Where can I buy 3VA1116-1AA36-0HH0?

This part is sourced to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
3VA1116-1AA36-0HH0