Skip to main content
Siemens 3VA1116-1AA42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA42-0AA0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA42-0AA0
Active

Siemens SENTRON 3VA1116-1AA42-0AA0, switch disconnector in MCCB design, IEC frame 160, 4-pole, SD100, In=160 A, without overload or short-circuit protection, busbar connection front terminal.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA42-0AA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1116-1AA42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Power loss, max.38 W
3VA1116-1AA42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1116-1AA42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width101.6 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1116-1AA42-0AA0 is a 4-pole switch disconnector in MCCB-style construction, rated 160 A continuous at 40 °C and carrying a 690 V AC / 600 V DC operating voltage. This is a pure disconnecting switch — no overload or short-circuit protection, no trip indicator, no undervoltage release, and no auxiliary contacts built in. That makes it a straightforward, high-current isolation point for a panel feeder or a machine supply, sized for the 160 A frame.

Thermal derating and real-world capacity

Above that it derates gradually: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. If your enclosure runs hot near the top of the ambient range, you lose 10 A off the headline number. That 150 A at 70 °C is still a solid disconnect rating for a 150 A feeder or a 110 kW motor at 400 V (roughly 200 FLA), but the thermal curve matters for a tight busway tap.

The front-terminal busbar connection simplifies mounting against a backplate.