Skip to main content
Siemens 3VA1116-1AA42-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA42-0AH0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA42-0AH0

Siemens SENTRON 3VA1116-1AA42-0AH0, IEC frame 160, 4-pole switch disconnector, In=160 A, without overload or short-circuit protection, busbar connection, front terminals, IP40 front, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA42-0AH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1116-1AA42-0AH0 — Ratings
ParameterValue
Number of poles4
Power loss, max.38 W
3VA1116-1AA42-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA42-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1116-1AA42-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA42-0AH0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1116-1AA42-0AH0 is a 4-pole switch disconnector in the 3VA1 IEC frame 160 platform, rated for 160 A continuous current (Iu) with no integral overload or short-circuit protection — it is a pure disconnect, not a circuit breaker. Its job is to provide visible isolation of a downstream load for lockout/tagout, maintenance access, or branch-circuit disconnection in a panel. The part carries a rated insulation voltage (Ui) of 800 V and a maximum operational voltage of 690 V AC 50/60 Hz or 600 V DC, so it suits both AC distribution and DC bus circuits up to those levels. The front terminals accept busbar connection — typical for a main-disconnect or panel-feed application where the switch ties directly to a busbar stack rather than individual cable lugs.

Short-circuit withstand and endurance

Because this is a switch disconnector without overcurrent trip elements, its fault-closing and short-time withstand ratings define the limits. The part is rated for 2 kA at both 1-second and 0.5-second intervals — meaning it must be backed by an upstream overcurrent protective device (fuse or MCCB) rated to limit let-through energy below that threshold. The mechanical endurance is 15,000 operating cycles, which is typical for a panel disconnect expected to see daily switching but not continuous high-speed operation.

The 3VA1116-1AA42-0AH0 measures 70 mm deep, 101.6 mm wide, and 130 mm tall. The 101.6 mm width corresponds to a 4-pole frame in the 3VA1 series — it occupies the same DIN-rail or mounting-plate footprint as other 4-pole 3VA1 devices, so a panel laid out for a 4-pole 3VA1 MCCB can accept this switch disconnector without re-drilling.

Temperature range and power dissipation

The motor-drive option (product extension optional) allows remote motorized operation for automated disconnection sequences.

Frequently asked questions

How do I get current pricing and availability for 3VA1116-1AA42-0AH0?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation at quote time.

Will 3VA1116-1AA42-0AH0 drop into a panel specified around 3VA1010-2ED42-0AE0 without rewiring?

Both parts share the same 70 mm depth, 101.6 mm width, and 130 mm height, so the physical footprint is identical. However, the 3VA1010-2ED42-0AE0 is a molded case circuit breaker with lug terminals for cable connection, while the 3VA1116-1AA42-0AH0 is a switch disconnector with busbar connection — the terminal type differs, so the busbar or cable interface may require adaptation.

What are the key ratings of 3VA1116-1AA42-0AH0?

Rated continuous current Iu is 160 A. Maximum operational voltage is 690 V AC 50/60 Hz and 600 V DC. Rated insulation voltage Ui is 800 V. Short-time withstand is 2 kA at 1 second and 2 kA at 0.5 seconds. Mechanical endurance is 15,000 operating cycles.

MPN
3VA1116-1AA42-0AH0