Siemens 3VA1116-1AA42-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA42-0DH0 Switch Disconnector, 160 A, 4-Pol

MPN3VA1116-1AA42-0DH0

Siemens SENTRON 3VA1116-1AA42-0DH0, IEC frame 160 switch disconnector, 4-pole, In=160 A, busbar connection, IP40 front, with undervoltage release 208-230 V AC, 2 HQ auxiliary switches + 1 HQ trip alarm switch.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA42-0DH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1116-1AA42-0DH0 — Ratings
ParameterValue
Number of poles4
Power loss, max.38 W
3VA1116-1AA42-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA42-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1116-1AA42-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA42-0DH0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

It is not a molded case circuit breaker — it provides no overload or short-circuit protection. Its job is safe isolation under load, not fault interruption. The 4-pole configuration switches three phases plus neutral, which matters for TN-S or TN-C-S systems where you need full isolation of the neutral conductor. Rated insulation voltage is 800 V, with maximum operational voltage 690 V AC 50/60 Hz and 600 V DC. That DC rating is useful for 480 VDC bus applications common in data-center or solar-string isolation.

Built-in auxiliary and release package

This variant ships with an integrated undervoltage release (UVR) rated 208-230 V AC, plus two HQ auxiliary switches and one HQ trip alarm switch — three CO contacts total. The UVR ensures the disconnector opens automatically if control voltage drops, a standard requirement for safety isolation in conveyor or machine-tool circuits. The auxiliary and alarm contacts feed status back to a PLC or panel indication without needing separate add-on modules. The main current circuit uses busbar connection on front terminals — designed for direct busbar stabs or bolted link bars, not lug or box terminals. That means the panel bus must be planned around this connection style; retrofitting into a lug-terminated panel requires an adapter kit. Optional motor drive is supported for remote switching.

Mechanical and environmental limits

Mechanical endurance is rated at 15 000 operating cycles — typical for a switch disconnector in this frame class, suitable for daily isolation duty but not for frequent switching as a load-break device.

Frequently asked questions

Where can I buy 3VA1116-1AA42-0DH0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What is the difference between this switch disconnector and the 3VA1112-5EF32-0CA0 MCCB?

The 3VA1112-5EF32-0CA0 is a 3-pole molded case circuit breaker with thermal-magnetic overcurrent protection (TM240 release) and a 125 A frame, while this 3VA1116-1AA42-0DH0 is a 4-pole switch disconnector with no overcurrent protection. The MCCB has interrupting ratings up to 187 kA at 240 V; the disconnector has no SCCR because it is not designed to clear faults. They share the same 70 mm depth and 130 mm height, but the disconnector is wider at 101.6 mm vs 76.2 mm for the 3-pole MCCB. They are not drop-in interchangeable — the disconnector requires busbar connection and has different termina

What compliance documentation is available for this part?

The part carries Siemens SENTRON branding and is designed to IEC standards (DIN EN 81346-2 reference code Q). Specific certifications (UL, CSA, CE, RoHS, REACH) are not listed in the available specifications; consult the full manufacturer declaration for your jurisdiction.

MPN
3VA1116-1AA42-0DH0