3VA1116-3ED26-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1116-3ED26-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Rated insulation voltage Ui500 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Power loss, max.25.34 W
3VA1116-3ED26-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1116-3ED26-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-3ED26-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1116-3ED26-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-3ED26-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

It carries 160 A continuously at 40 °C through 50 °C, then derates to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C — so in a warm panel you lose only about 6 % of the current rating at the top of the operating range. The interrupting capacity hits 75.6 kA at 240 V AC and 52.5 kA at 415 V AC, which gives solid headroom for most industrial distribution boards with high fault current.

Thermal-magnetic release and coordination

The overcurrent release is a TM210 (thermal-magnetic, fixed settings) with LI protection — long-time and instantaneous. It's a straight line-protection breaker: no ground-fault monitoring, no motor drive.

Frequently asked questions

How do I get current pricing and availability for 3VA1116-3ED26-0AA0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; we source through independent distribution and can quote to your required quantity and delivery window.

What is 3VA1116-3ED26-0AA0's interrupting capacity at 240 V?

It is rated 75.6 kA at 240 V AC, and 52.5 kA at 415 V AC — suitable for high-fault-current industrial panels.

Will 3VA1116-3ED26-0AA0 drop into a panel that was specified around 3VA1112-5EE32-0AA0 without rewiring?

Both are 2-pole SENTRON MCCBs on the same 50.8 mm width, so the physical footprint and DIN-rail mounting are identical. The 3VA1116-3ED26-0AA0 is a 160 A frame with a TM210 release; the 3VA1112-5EE32-0AA0 is a different current rating and release type. Verify the load current and trip curve match your application before swapping — the panel wiring itself does not need rework, but the breaker must be correctly sized.