Skip to main content
Siemens 3VA1116-3ED26-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-3ED26-0AA0 SENTRON MCCB, 160 A, 2-Pole, 75.6

MPN3VA1116-3ED26-0AA0
Active

Siemens SENTRON 3VA1116-3ED26-0AA0, 2-pole molded case circuit breaker, 160 A (40 °C), 75.6 kA at 240 V AC, TM210 release, line protection, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-3ED26-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1116-3ED26-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Rated insulation voltage Ui500 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Power loss, max.25.34 W

Protection & Trip Unit

3VA1116-3ED26-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1116-3ED26-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-3ED26-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1116-3ED26-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-3ED26-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

What this MCCB delivers

The Siemens 3VA1116-3ED26-0AA0 is a 2-pole SENTRON molded case circuit breaker rated for line protection. It carries 160 A continuously at 40 °C through 50 °C, then derates to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C — so in a warm panel you lose only about 6 % of the current rating at the top of the operating range. The interrupting capacity hits 75.6 kA at 240 V AC and 52.5 kA at 415 V AC, which gives solid headroom for most industrial distribution boards with high fault current.

Thermal-magnetic release and coordination

The overcurrent release is a TM210 (thermal-magnetic, fixed settings) with LI protection — long-time and instantaneous. No trip indicator, no undervoltage release, no communication module. It's a straight line-protection breaker: no ground-fault monitoring, no motor drive. The rated insulation voltage is 500 V, and the maximum operating voltage is 415 V AC or 250 V DC. Power loss at full load is 25.34 W — plan for that in a sealed enclosure.

Mounting and environment

Dimensions are 130 mm high, 50.8 mm wide, 70 mm deep. Front protection is IP40 — fine for a dry indoor panel, but not washdown. Storage range is -40 °C to 80 °C; operating range is -25 °C to 70 °C. Mounts on a DIN rail or direct panel; the 2-pole width (50.8 mm) is standard for a 160 A frame.

Frequently asked questions

How do I get current pricing and availability for 3VA1116-3ED26-0AA0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; we source through independent distribution and can quote to your required quantity and delivery window.

What is 3VA1116-3ED26-0AA0's interrupting capacity at 240 V?

It is rated 75.6 kA at 240 V AC, and 52.5 kA at 415 V AC — suitable for high-fault-current industrial panels.

Will 3VA1116-3ED26-0AA0 drop into a panel that was specified around 3VA1112-5EE32-0AA0 without rewiring?

Both are 2-pole SENTRON MCCBs on the same 50.8 mm width, so the physical footprint and DIN-rail mounting are identical. The 3VA1116-3ED26-0AA0 is a 160 A frame with a TM210 release; the 3VA1112-5EE32-0AA0 is a different current rating and release type. Verify the load current and trip curve match your application before swapping — the panel wiring itself does not need rework, but the breaker must be correctly sized.

MPN
3VA1116-3ED26-0AA0