It carries 160 A continuously up to 50 °C, then derates to 150 A at 70 °C — so on a warm panel day you still have headroom for a full 150 A feeder. Breaking capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, and 11.9 kA at 690 V, which covers most industrial distribution panels without needing a current-limiting upstream breaker.
Built-in undervoltage release and auxiliary switch set
That saves wiring a separate UVR module and a panel cutout.
Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard SENTRON 3VA frame size that drops into existing MCCB panel cutouts and busbar systems.