Specifications

3VA1116-3EF32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1116-3EF32-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1116-3EF32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1116-3EF32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-3EF32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1116-3EF32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-3EF32-0CC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1116-3EF32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated for a continuous current Iu of 160 A at 40 °C, holding that rating up to 50 °C before a gentle derating curve begins — 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. That means for most panel environments below 50 °C, you get full 160 A capacity without headroom calculations; above that, the thermal curve is predictable and published. Breaking capacity is specified across four voltage levels: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. The 415 V figure is the one most often checked for European 400 V distribution — 52.5 kA gives solid selectivity headroom against most upstream transformers in a standard industrial panel. The 690 V rating is lower but still covers the majority of motor-circuit fault currents on 690 V systems. The overcurrent release is a TM240 — a thermal-magnetic unit with a 240 A frame, set here for a 160 A continuous rating. This is a fixed-trip breaker for straightforward line protection where you don't need remote monitoring or adjustable curves.

Dimensions are 70 mm depth, 76.2 mm width, and 130 mm height — a compact 3-pole footprint that fits standard SENTRON mounting plates and busbar systems. The 76.2 mm width is exactly 3 module spaces (each 25.4 mm) on a DIN rail or panel-mount grid, so it aligns with the modular spacing used across the SENTRON family. The storage minimum of -40 °C is relevant for cold warehouses or unheated shipping; the operating minimum of -25 °C covers most outdoor cabinet installations in temperate climates.

Frequently asked questions

What is the breaking capacity of 3VA1116-3EF32-0CC0 at 415 V?

At 415 V the breaking capacity is 52.5 kA. This is the most commonly checked figure for European 400 V distribution panels and provides good selectivity headroom for standard industrial transformer ratings.

What does the TM240 release mean on this MCCB?

TM240 designates a thermal-magnetic overcurrent release with a 240 A frame, set here for a 160 A continuous rating. The thermal element handles overload protection; the magnetic element handles short-circuit. No electronic adjustment, communication, or ground-fault monitoring is included.