Skip to main content
Siemens 3VA1116-3EF32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-3EF32-0CC0 SENTRON MCCB, 160 A, 3-pole, TM24

MPN3VA1116-3EF32-0CC0

Siemens SENTRON 3VA1116-3EF32-0CC0, molded case circuit breaker, 3-pole, 160 A, TM240 overcurrent release, 75.6 kA at 240 V, 2 auxiliary switches HQ, undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-3EF32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1116-3EF32-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA

Protection & Trip Unit

3VA1116-3EF32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1116-3EF32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-3EF32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1116-3EF32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-3EF32-0CC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What the ratings mean for fit

The Siemens SENTRON 3VA1116-3EF32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated for a continuous current Iu of 160 A at 40 °C, holding that rating up to 50 °C before a gentle derating curve begins — 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. That means for most panel environments below 50 °C, you get full 160 A capacity without headroom calculations; above that, the thermal curve is predictable and published. Breaking capacity is specified across four voltage levels: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. The 415 V figure is the one most often checked for European 400 V distribution — 52.5 kA gives solid selectivity headroom against most upstream transformers in a standard industrial panel. The 690 V rating is lower but still covers the majority of motor-circuit fault currents on 690 V systems. The overcurrent release is a TM240 — a thermal-magnetic unit with a 240 A frame, set here for a 160 A continuous rating. The TM designation means the thermal element handles overload protection and the magnetic element handles short-circuit; no electronic adjustment, no communication module, no ground-fault monitoring. This is a fixed-trip breaker for straightforward line protection where you don't need remote monitoring or adjustable curves.

Lifecycle and sourcing reality

Rated insulation voltage Ui is 800 V, and the protection class on the front is IP40 — suitable for enclosed panel mounting where the front face is behind a door. The auxiliary contact version is 2 auxiliary switches HQ (high-qualified), and the breaker includes an undervoltage release (UVR) as standard. The integrated auxiliary trip order code is 3VA9608-0BB24, which is the specific UVR module that ships with this variant.

Panel integration and dimensions

Dimensions are 70 mm depth, 76.2 mm width, and 130 mm height — a compact 3-pole footprint that fits standard SENTRON mounting plates and busbar systems. The 76.2 mm width is exactly 3 module spaces (each 25.4 mm) on a DIN rail or panel-mount grid, so it aligns with the modular spacing used across the SENTRON family. Depth of 70 mm means it clears most 200 mm deep enclosures with room for wiring and busbar connections behind the breaker. Operating temperature range is -25 °C to 70 °C, storage range -40 °C to 80 °C. The storage minimum of -40 °C is relevant for cold warehouses or unheated shipping; the operating minimum of -25 °C covers most outdoor cabinet installations in temperate climates. The latching endurance is rated at 15,000 operations — a mechanical endurance figure that indicates the breaker is designed for occasional switching, not daily load-break duty.

Frequently asked questions

What is the breaking capacity of 3VA1116-3EF32-0CC0 at 415 V?

At 415 V the breaking capacity is 52.5 kA. This is the most commonly checked figure for European 400 V distribution panels and provides good selectivity headroom for standard industrial transformer ratings.

What does the TM240 release mean on this MCCB?

TM240 designates a thermal-magnetic overcurrent release with a 240 A frame, set here for a 160 A continuous rating. The thermal element handles overload protection; the magnetic element handles short-circuit. No electronic adjustment, communication, or ground-fault monitoring is included.

Does 3VA1116-3EF32-0CC0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as standard. The specific auxiliary release module order code is 3VA9608-0BB24.

Where can I buy 3VA1116-3EF32-0CC0 and how is it quoted?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing; the quote will reflect the landed cost to your dock.

MPN
3VA1116-3EF32-0CC0