Skip to main content
Siemens 3VA1116-3EF32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-3EF32-0CH0 SENTRON MCCB, 160 A, 75.6 kA

MPN3VA1116-3EF32-0CH0

Siemens SENTRON 3VA1116-3EF32-0CH0, molded case circuit breaker, 3-pole, 160 A at 40 °C, 75.6 kA breaking capacity at 240 V, line protection, with undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-3EF32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11163EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1116-3EF32-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.40.5 W

Protection & Trip Unit

3VA1116-3EF32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1116-3EF32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-3EF32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1116-3EF32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-3EF32-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB carries and where it fits

The Siemens SENTRON 3VA1116-3EF32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection in distribution panels. It carries 160 A continuously at 40 °C ambient, with a slight thermal derating curve that holds 150 A at 70 °C — useful when the breaker shares a warm enclosure with other heat sources. The 75.6 kA breaking capacity at 240 V AC gives it headroom for high-fault installations; at 415 V it still interrupts 52.5 kA, and at 690 V it holds 11.9 kA. The rated insulation voltage of 800 V covers most industrial supply voltages without additional derating. This is a line-protection design — no ground-fault monitoring, no communication module, no voltage-trip coil. It ships with an undervoltage release (UVR) and a factory-fitted auxiliary switch block: two auxiliary contacts plus one trip-alarm switch (HQ). The auxiliary switch design is 2 auxiliary switches + 1 trip alarm switch HQ, which gives separate signaling for breaker position and fault condition. The 70 mm depth, 76.2 mm width, and 130 mm height fit standard Siemens SENTRON panel footprints; the 3-pole block occupies three 25.4 mm module positions on the DIN rail.

Thermal performance and power loss

The breaker dissipates a maximum of 40.5 W at rated load — a figure to factor into enclosure thermal calculations, especially when multiple breakers are ganged. The operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C. The continuous current rating holds flat at 160 A from 40 °C through 50 °C, then begins a gradual derating: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. This thermal curve is typical for thermal-magnetic MCCBs and governs the real-world ampacity in warm panels.

Breaking capacity by voltage

The interrupting rating varies with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. These figures define the maximum fault current the breaker can safely clear at each voltage level — critical for coordination studies and SCCR compliance in the panel label. The 75.6 kA at 240 V covers most North American 240/120 V distribution; the 52.5 kA at 415 V suits European 400 V networks.

Dimensions and panel fit

The 3VA1116-3EF32-0CH0 measures 70 mm deep, 76.2 mm wide, and 130 mm tall. The 76.2 mm width corresponds to three 25.4 mm module positions on a standard DIN rail — the usual SENTRON mounting pitch. The 70 mm depth leaves clearance for rear-connected busbars or cable lugs in a typical 200 mm deep enclosure. The trip indicator is present, giving a visual flag when the breaker has tripped on fault.

Frequently asked questions

How do I get current pricing and availability for 3VA1116-3EF32-0CH0?

The part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What are the key ratings for 3VA1116-3EF32-0CH0?

It is a 3-pole MCCB rated 160 A at 40 °C, with 75.6 kA breaking capacity at 240 V, 52.5 kA at 415 V, and 11.9 kA at 690 V. Rated insulation voltage is 800 V.

What is the depth of 3VA1116-3EF32-0CH0?

The depth is 70 mm (2.76 in). Width is 76.2 mm (3 in), height is 130 mm (5.12 in).

Does 3VA1116-3EF32-0CH0 include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) and a factory-fitted auxiliary switch block: two auxiliary switches plus one trip alarm switch HQ.

MPN
3VA1116-3EF32-0CH0