Skip to main content
Siemens 3VA1116-3EF32-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-3EF32-0HH0 SENTRON MCCB, 160 A, 75.6 kA at 2

MPN3VA1116-3EF32-0HH0

Siemens SENTRON 3VA1116-3EF32-0HH0, molded case circuit breaker, 3-pole, line protection, 160 A (40 °C), 75.6 kA at 240 VAC, with shunt trip (STL) and 2 aux + 1 trip alarm switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-3EF32-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11163EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1116-3EF32-0HH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.38 W
3VA1116-3EF32-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1116-3EF32-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-3EF32-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1116-3EF32-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-3EF32-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It carries a 160 A continuous rating at 40 °C, with the full thermal derating curve available: still 160 A at 50 °C, 158 A at 55 °C, and 150 A at 70 °C. That derating profile means you can run it near its nameplate in most ventilated enclosures without oversizing. Breaking capacity is the headline here: 75.6 kA at 240 VAC, 52.5 kA at 415 VAC, 32 kA at 440 VAC, and 11.9 kA at 500/690 VAC. That 75.6 kA at 240 V gives strong selectivity headroom on the secondary side of a 480 V–208Y/120 V transformer — a common panel feed scenario.

Accessories and integration

The basic switch variant is 3VA11163EF320AA0. The auxiliary and alarm switches give status feedback to a control system or SCADA input.

The depth is shallow enough that it clears most standard gland plates and backpanel wiring troughs.

Frequently asked questions

Where can I buy 3VA1116-3EF32-0HH0 and how do I get a price?

Sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1116-3EF32-0HH0 at 415 V?

52.5 kA at 415 VAC. Also rated 75.6 kA at 240 V, 32 kA at 440 V, and 11.9 kA at 500/690 V.

What accessories are included with 3VA1116-3EF32-0HH0?

Includes a shunt trip (STL) release, two auxiliary switches, and one trip alarm switch (HQ). The basic switch variant is 3VA11163EF320AA0.

MPN
3VA1116-3EF32-0HH0