It carries a 160 A continuous rating at 40 °C ambient, with a 3-pole configuration and a TM240 thermal-magnetic overcurrent release that provides both overload and short-circuit protection in a single unit. Breaking capacity is 75.6 kA at 240 V AC, 52.5 kA at 415 V, and 32 kA at 440 V — figures that determine whether this breaker clears a fault without upstream damage in your specific system voltage. At 500 V and 690 V the rating drops to 11.9 kA, so verify your available fault current at the point of installation.
Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard footprint that fits most DIN-rail or panel-mount MCCB enclosures.