Skip to main content
Siemens 3VA1116-3EF36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-3EF36-0JA0 SENTRON MCCB, 160 A, 3-Pole, TM24

MPN3VA1116-3EF36-0JA0

Siemens SENTRON 3VA1116-3EF36-0JA0, molded case circuit breaker, line protection, 3-pole, 160 A rated continuous current, TM240 overcurrent release, 75.6 kA breaking capacity at 240 V, shunt trip design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-3EF36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1116-3EF36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA

Protection & Trip Unit

3VA1116-3EF36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1116-3EF36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-3EF36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1116-3EF36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-3EF36-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

160 A MCCB with TM240 release — line protection for distribution panels

The Siemens SENTRON 3VA1116-3EF36-0JA0 is a 3-pole molded case circuit breaker rated for 160 A continuous current (Iu) at 40 °C, with the TM240 thermal-magnetic overcurrent release. The TM240 designation means the thermal trip element is calibrated for a 240 A frame, but the breaker's continuous rating is set at 160 A — so the trip curve starts its thermal bend above 160 A, not 240 A. This is a line protection version, meaning it's intended for feeder and main distribution duty, not motor branch-circuit protection where a separate overload relay would be required. Breaking capacity is specified at four voltage levels: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. For a 160 A frame, the 52.5 kA at 415 V is the figure that governs most 400 V-class industrial distribution panels — it tells you the breaker can safely interrupt a fault up to that current without welding contacts or venting arc gas into the enclosure. The 690 V rating (10.5 kA) covers the less common 690 V line-to-line systems found in mining or marine installations. The breaker includes a shunt trip release (STL) as the auxiliary release design, which allows remote tripping via a control voltage — useful for emergency-stop circuits or supervisory shutdown sequences. The integrated auxiliary trip order code is 3VA9688-0BL32, which is the specific shunt trip module that mates with this breaker frame. No undervoltage release, no auxiliary contacts, no communication function, and no ground-fault monitoring are fitted on this variant.

Current derating and thermal limits

The 160 A rating holds from 40 °C through 50 °C ambient. At 55 °C it derates to 153.6 A, at 60 °C to 150.4 A, at 65 °C to 147.2 A, and at 70 °C to 144 A (–). The operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. The IP40 front protection means the breaker face is protected against solid objects over 1 mm — typical for a panel-mounted device where the enclosure provides the overall IP rating.

Physical footprint and panel integration

Dimensions: 130 mm height, 76.2 mm width, 70 mm depth. The 76.2 mm width (3 inches) is the standard 3-pole MCCB footprint for this current class — it fits the same panel cutout as other 160 A 3-pole SENTRON breakers. The 70 mm depth includes the arc chamber and terminal space; verify clearance behind the panel for the shunt trip wiring and any auxiliary modules you add.

Frequently asked questions

How do I get current pricing and availability for 3VA1116-3EF36-0JA0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution channels; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1116-3EF36-0JA0 at 415 V?

52.5 kA at 415 V. This is the rating that governs most 400 V-class industrial distribution panels for this 160 A frame.

What does the TM240 release designation mean on this breaker?

TM240 indicates the thermal-magnetic trip unit is built on a 240 A frame, but the breaker's continuous current rating (Iu) is set to 160 A. The thermal trip element starts its bend above 160 A, not 240 A — the frame rating is the maximum the trip unit can be adjusted to, not the actual rating of this variant.

MPN