Skip to main content
Siemens 3VA1116-3FF46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-3FF46-0AA0 SENTRON 4-Pole MCCB, 160 A, 75.6

MPN3VA1116-3FF46-0AA0
Active

Siemens SENTRON 3VA1116-3FF46-0AA0, 4-pole molded case circuit breaker, 160 A, TM240 thermal-magnetic release, 75.6 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-3FF46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1116-3FF46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.38 W
3VA1116-3FF46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1116-3FF46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-3FF46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1116-3FF46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-3FF46-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Siemens 3VA1116-3FF46-0AA0 — 160 A 4-Pole MCCB for Line Protection

The Siemens 3VA1116-3FF46-0AA0 is a SENTRON 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 160 A at 40 °C with a TM240 thermal-magnetic release. Its interrupting capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — numbers that tell you this breaker handles high-fault utility feeds or large transformer secondaries without cascading upstream. The 4-pole configuration (3 phases + switched neutral at 50% N protection) makes it suitable for three-phase systems where neutral isolation is required, common in European-style distribution panels. Front protection is IP40 — fine for enclosed panel mounting where no washdown or dust ingress is expected.

Breaking Capacity Across Voltages — Selectivity Planning

The 3VA1116-3FF46-0AA0's breaking capacity drops from 75.6 kA at 240 V to 52.5 kA at 415 V, then to 32 kA at 440 V, and further to 11.9 kA at both 500 V and 690 V. For a site electrical engineer coordinating with upstream feeders, the 415 V figure (52.5 kA) is the one that typically governs in European 400 V networks — it gives you headroom for most industrial transformer ratings up to 2 MVA. At 690 V, the 11.9 kA limit means this breaker is not the right choice for high-fault 690 V drives or mining substations; step up to a higher-rated 3VA frame for those.

Thermal Derating — Continuous Current vs Ambient

The breaker holds 160 A continuously from 40 °C through 50 °C, then derates gradually: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. For a panel OEM packing breakers into a non-ventilated enclosure, that 150 A floor at 70 °C is the safe number to use for the BOM line — the breaker won't nuisance-trip even if internal ambient rises near its operating maximum of 70 °C.

Dimensions: 130 mm height, 101.6 mm width, 70 mm depth. The 70 mm depth is relatively shallow for a 160 A 4-pole MCCB — it fits into compact 400 mm deep enclosures where deeper breakers would force a wider gland plate or a deeper box. Width of 101.6 mm (4 inches) is standard for a 4-pole frame; it occupies four 25 mm module spaces on a DIN rail if using an adapter, though the 3VA series typically bolts directly to a mounting plate. An optional motor drive is available (Product Extension / Optional / Motor Drive = Yes) for remote trip or reclose applications.

Frequently asked questions

Where can I buy 3VA1116-3FF46-0AA0 and how do I get a price?

The 3VA1116-3FF46-0AA0 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 3VA1116-3FF46-0AA0's interrupting capacity at 415 V?

The interrupting capacity is 52.5 kA at 415 V, which is the governing figure for most European 400 V industrial networks.

What is the continuous current rating of 3VA1116-3FF46-0AA0 at 40 °C?

The continuous current Iu is 160 A at 40 °C, and it holds that rating through 50 °C before derating.

MPN
3VA1116-3FF46-0AA0