It's rated for a breaking capacity of 25 kA at 415 V (class N), with a fixed 160 A thermal-magnetic overload (TM210) and fixed short-circuit pickup at 10 x In.
The fixed Ir=160 A means no adjustment dial; you size the breaker to the load, not the other way around. Fixed Ii=10 x In (1600 A magnetic trip) suits motor or transformer inrush without nuisance tripping, but won't coordinate with a feeder breaker that has a lower instantaneous threshold — check your selectivity study.