What this 3VA1 frame 160 breaker delivers
Trip settings and protection profile
The TM220 trip provides adjustable overload protection from 112 A to 160 A (Ir), with a fixed short-circuit pickup at 10 x In (Ii = 1600 A). The 100% N-conductor protection means the neutral pole is fully rated, not reduced — important for 4-wire systems where harmonic currents or unbalanced loads can push neutral current near phase levels. A nut keeper kit is included for the DC Power OEM variant destined for China.
