Skip to main content
Siemens 3VA1116-3GE46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-3GE46-0AA0 SENTRON MCCB, 160 A, 4-Pole, 75.6

MPN3VA1116-3GE46-0AA0
Active

Siemens SENTRON 3VA1116-3GE46-0AA0, molded case circuit breaker, 4-pole, 160 A, TM220 thermal-magnetic release, breaking capacity 75.6 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-3GE46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1116-3GE46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.38 W
3VA1116-3GE46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1116-3GE46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-3GE46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1116-3GE46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-3GE46-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

SENTRON 3VA1116-3GE46-0AA0 — 160 A MCCB, 4-Pole, TM220 Release

Breaking capacity runs 75.6 kA at 240 V AC, 52.5 kA at 415 V AC, and 32 kA at 440 V AC, so it handles high-fault utility feeds or transformer secondaries without cascading upstream.

Thermal Derating and Voltage Ratings

Full 160 A rating holds from 40 °C through 50 °C; above that it derates to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. That matters for a panel running warm — you don't lose headroom until the ambient passes 50 °C. Breaking capacity holds at 11.9 kA on 500 V and 690 V systems, so it's usable on 480/277 V and 600 V industrial feeds.

Footprint is 101.6 mm wide by 130 mm tall by 70 mm deep — a standard 4-pole MCCB width that drops into a SENTRON panel or a generic DIN-rail enclosure with the appropriate mounting base. Max power loss is 38 W, so factor that into the enclosure thermal budget.

Frequently asked questions

Where can I buy 3VA1116-3GE46-0AA0 and get a price?

This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request for current pricing and availability.

What is the breaking capacity of 3VA1116-3GE46-0AA0 at different voltages?

Breaking capacity is 75.6 kA at 240 V AC, 52.5 kA at 415 V AC, 32 kA at 440 V AC, and 11.9 kA at both 500 V and 690 V AC.

What type of overcurrent release does 3VA1116-3GE46-0AA0 use?

It uses a TM220 thermal-magnetic release — fixed thermal and magnetic trip settings, no electronic adjustment.

MPN
3VA1116-3GE46-0AA0