Skip to main content
Siemens 3VA1116-3GF46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-3GF46-0AA0 SENTRON MCCB, 160 A, 4-Pole

MPN3VA1116-3GF46-0AA0
Active

Siemens SENTRON 3VA1116-3GF46-0AA0, molded case circuit breaker, 160 A, 4-pole, TM240 thermal-magnetic release, line protection design, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-3GF46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1116-3GF46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.38 W

Protection & Trip Unit

3VA1116-3GF46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1116-3GF46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-3GF46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1116-3GF46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-3GF46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

160 A continuous, 4-pole — line protection for distribution panels

The Siemens SENTRON 3VA1116-3GF46-0AA0 is a 160 A molded case circuit breaker (MCCB) with a 4-pole configuration, designed for line protection in main distribution panels. Its TM240 thermal-magnetic release provides overload and short-circuit protection, with a continuous current rating of 160 A that holds up to 50 °C ambient — at 55 °C it derates to 158 A, and at 70 °C it still carries 150 A, so the thermal curve is manageable for most enclosed panel layouts. Breaking capacity varies by system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That spread tells you the 3VA1116-3GF46-0AA0 is sized for 400 V-class distribution where fault currents are moderate — it is not a high-fault 690 V breaker, but at 240 V it handles serious industrial fault levels.

Mounting and integration — DIN-rail footprint

The breaker measures 101.6 mm wide, 130 mm tall, and 70 mm deep — a standard 4-pole MCCB footprint that snaps onto DIN rail in the panel. Front IP40 protection means it is suited for general indoor distribution boards where tools or fingers might contact the front face but not for washdown zones. No undervoltage release, no communication module, no ground-fault monitoring on this variant — it is a straight thermal-magnetic line protection device, so plan external accessories if those functions are needed downstream.

Frequently asked questions

What is the breaking capacity of 3VA1116-3GF46-0AA0 at 415 V?

52.5 kA at 415 V, which covers most 400 V-class industrial distribution fault levels.

Where can I buy 3VA1116-3GF46-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time.

Does the 3VA1116-3GF46-0AA0 include an undervoltage release or communication?

No — this variant has no undervoltage release, no communication function, and no ground-fault monitoring. It is a straight thermal-magnetic line protection device.

MPN
3VA1116-3GF46-0AA0