Skip to main content
Siemens 3VA1116-4ED26-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-4ED26-0AA0 SENTRON MCCB, 160A, 2-Pole, 121kA

MPN3VA1116-4ED26-0AA0
Active

Siemens SENTRON 3VA1116-4ED26-0AA0, 2-pole molded case circuit breaker, 160 A at 40 °C, TM210 thermal-magnetic release, 121 kA at 240 V AC, 75.6 kA at 415 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-4ED26-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1116-4ED26-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Rated insulation voltage Ui500 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Power loss, max.25.34 W
3VA1116-4ED26-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1116-4ED26-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-4ED26-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1116-4ED26-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-4ED26-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1116-4ED26-0AA0 is a 2-pole molded case circuit breaker (MCCB) rated 160 A continuous at 40 °C, with a TM210 thermal-magnetic overcurrent release providing LI (long-time and instantaneous) protection. Its interrupting capacity reaches 121 kA at 240 V AC and 75.6 kA at 415 V AC — numbers that matter when you're coordinating selectivity downstream of a transformer or tying into a high-fault bus.

Deployment context

The 70 mm depth and 50.8 mm width fit standard SENTRON 3VA panel footprints, so it swaps into existing 2-pole slots without re-drilling.

Frequently asked questions

Where can I buy 3VA1116-4ED26-0AA0 and how do I get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, no stock or lead-time figures published here.

What is the breaking capacity of this MCCB at 240 V and 415 V?

It interrupts 121 kA at 240 V AC and 75.6 kA at 415 V AC, giving strong fault-current headroom for most industrial services.

Will 3VA1116-4ED26-0AA0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

Both are 2-pole SENTRON 3VA breakers with the same 50.8 mm width and 70 mm depth, so the mechanical footprint is identical. The difference is in the release — this one uses a fixed TM210 thermal-magnetic trip, while the 3VA1110-5ED36-0AC0 carries a different trip curve. Verify the trip settings match your coordination study before swapping.

What compliance documentation does this brand provide for 3VA1116-4ED26-0AA0?

Siemens SENTRON MCCBs carry CE marking, UL/CSA recognition, and IEC 60947-2 certification. RoHS and REACH declarations are available from Siemens documentation. The reference code per IEC 81346-2 is Q.

MPN