Skip to main content
Siemens 3VA1116-4FE42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-4FE42-0AA0 SENTRON MCCB, 80 A, 4-Pole, 121 k

MPN3VA1116-4FE42-0AA0
Active

Siemens SENTRON 3VA1116-4FE42-0AA0, molded case circuit breaker, 4-pole, 80 A, TM220 release, line protection, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-4FE42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1116-4FE42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.38 W
3VA1116-4FE42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1116-4FE42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-4FE42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1116-4FE42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-4FE42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

What this 80 A MCCB delivers

Its interrupting capacity reaches 121 kA at 240 V and 75.6 kA at 415 V, which means it can safely clear high-fault currents on the secondary side of a step-down transformer or a 400 V bus without cascading upstream — a key selectivity consideration for site electrical engineers. The 70 mm depth and 101.6 mm width fit standard MCCB panel cutouts; the IP40 front rating means it is protected against solid objects larger than 1 mm but not sealed against moisture — suitable for indoor switchboards, not washdown environments.

No official successor has been announced for this order code. For a BOM line that requires this exact 80 A, 4-pole TM220 configuration, the 3VA1116-4FE42-0AA0 remains the direct fit.

Installation constraints

Verify your control scheme does not rely on shunt-trip or remote signaling before specifying. Maximum power loss is 38 W; ensure adequate ventilation in the panel to keep internal ambient below 70 °C operating limit.

Frequently asked questions

Where can I buy 3VA1116-4FE42-0AA0 and how do I get a price?

This part is sourced and quoted to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What are the key interrupting ratings for 3VA1116-4FE42-0AA0?

It interrupts 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

What is the operating temperature range for this MCCB?

It operates from -25 °C to 70 °C ambient, with thermal derating from 160 A at 40 °C down to 150 A at 70 °C.

MPN
3VA1116-4FE42-0AA0