160 A fixed rating, 4-pole, TM210 — line protection for distribution panels
Breaking capacity runs from 121 kA at 240 V down to 11.9 kA at 690 V, so the 415 V rating of 75.6 kA is the one to check against your available fault current.
Above that it derates linearly: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C.