160 A MCCB with TM210 release
The TM210 is a fixed thermal and fixed magnetic trip — no field-adjustable pickup — so it's a straight swap for a line-protection application where the load current is known and stable. Breaking capacity reaches 187 kA at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V — enough for high-fault utility feeds or transformer secondaries.
Above that it derates: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C.
Integration and auxiliary contacts
It ships with three auxiliary switches (HQ type) factory-fitted, so you get remote status indication without additional wiring.