The TM210 designation means the continuous current rating is 160 A, and it holds that full rating from 40 °C up through 50 °C ambient; above that it derates to 158 A at 55 °C and 150 A at 70 °C — a curve to check if your panel runs hot. Breaking capacity ranges from 187 kA at 240 V down to 17 kA at 500/690 V, so the available fault current at your service voltage determines whether this frame clears the fault without upstream coordination issues.
A mechanical trip indicator is present on the front — useful for a quick visual walk-down during troubleshooting.
Physical integration
No undervoltage release or communication module fitted from the factory, so if those are needed they must be added as separate accessories.