Skip to main content
Siemens 3VA1116-5ED32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-5ED32-0BC0 SENTRON MCCB, 160 A, 3-Pole

MPN3VA1116-5ED32-0BC0

Siemens SENTRON 3VA1116-5ED32-0BC0, molded case circuit breaker, 3-pole, 160 A rated continuous current, line protection, TM210 overcurrent release, 187 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-5ED32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1116-5ED32-0BC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1116-5ED32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1116-5ED32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-5ED32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1116-5ED32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-5ED32-0BC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

That 160 A holds flat through 50 °C; above that the thermal curve steps down to 153.6 A at 55 °C and 144 A at 70 °C, so if this breaker lives in a hot enclosure near other heat sources, you need to account for that derating on the load side. The TM210 overcurrent release handles the thermal-magnetic trip — fixed thermal and magnetic elements, no electronic adjustment. Line protection version means it's set up for feeder and distribution duty, not motor or generator protection.

Mounting and integration — fits a standard panel footprint

Width is 76.2 mm. Depth of 70 mm and height of 130 mm mean it clears most gland plates and back panels without interference. IP40 on the front keeps dust out of the mechanism. Comes with 2 auxiliary switches (HQ type) and an undervoltage release (UVR) integrated.

MPN
3VA1116-5ED32-0BC0