It carries a rated current of 160 A across an ambient temperature range of 40 °C to 50 °C, derating to 150 A at 70 °C — so the thermal trip curve is calibrated for real panel conditions, not just a single number.
Breaking capacity — selectivity headroom
Breaking capacity is 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V.
Integration and auxiliary options