Skip to main content
Siemens 3VA1116-5EE32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-5EE32-0AG0 SENTRON MCCB, 160 A, 3-Pole, TM22

MPN3VA1116-5EE32-0AG0

Siemens SENTRON 3VA1116-5EE32-0AG0, molded case circuit breaker, 3-pole, 160 A, TM220 release, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-5EE32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB11

Ratings

3VA1116-5EE32-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1116-5EE32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220

Construction & Connection

3VA1116-5EE32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-5EE32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1116-5EE32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-5EE32-0AG0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What it is and what it does

The Siemens SENTRON 3VA1116-5EE32-0AG0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current, with a TM220 thermal-magnetic release — meaning it uses a bimetal element for overload protection and a magnetic coil for short-circuit interruption, both fixed-trip (non-adjustable for the thermal portion). Breaking capacity is 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — these are the maximum fault currents the breaker can safely interrupt at each voltage level, so for a 480 V panel the relevant figure is the 415 V or 440 V rating depending on the actual line-to-line voltage. Rated insulation voltage (Ui) is 800 V, which defines the maximum voltage the internal insulation can withstand continuously — important for verifying coordination with upstream switchgear in a 690 V system.

Thermal derating and ambient limits

The breaker carries its full 160 A from 40 °C through 50 °C ambient. Above that it derates: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. If the panel ambient runs hot — say near a drive stack — use the 55 °C or 60 °C column for sizing, not the 40 °C sticker. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. The storage limit governs handling and warehousing, not running conditions.

Physical fit and panel integration

Dimensions: 130 mm height, 76.2 mm width, 70 mm depth. The 70 mm depth is shallow enough for most 200 mm deep enclosures without crowding the gland plate; the 76.2 mm width (roughly 3 inches) fits a standard 3-pole MCCB footprint on a DIN rail or direct-mount backplate. Front protection is IP40 — splash-proof from the front but not sealed against hose-down. Suitable for indoor panel mounting; not for washdown zones without an additional enclosure.

Auxiliary contacts and release options

Comes with one auxiliary switch and one trip alarm switch (HP type) factory-fitted. No undervoltage release, no shunt trip, no ground-fault monitoring — those are separate add-on accessories if the application requires them. Trip indicator is present (mechanical flag on the front), and the latching endurance is rated at 15,000 operations — that's the mechanical life under no-load; electrical life will be lower and depends on the interrupted current.

MPN
3VA1116-5EE32-0AG0