Skip to main content
Siemens 3VA1116-5EE32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-5EE32-0AG0 SENTRON MCCB, 160 A, 3-Pole, TM22

MPN3VA1116-5EE32-0AG0

Siemens SENTRON 3VA1116-5EE32-0AG0, molded case circuit breaker, 3-pole, 160 A, TM220 release, 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-5EE32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA1116-5EE32-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1116-5EE32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
3VA1116-5EE32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-5EE32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1116-5EE32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-5EE32-0AG0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Breaking capacity is 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — these are the maximum fault currents the breaker can safely interrupt at each voltage level, so for a 480 V panel the relevant figure is the 415 V or 440 V rating depending on the actual line-to-line voltage.

Above that it derates: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C.

The 70 mm depth is shallow enough for most 200 mm deep enclosures without crowding the gland plate; the 76.2 mm width (roughly 3 inches) fits a standard 3-pole MCCB footprint on a DIN rail or direct-mount backplate. Front protection is IP40 — splash-proof from the front but not sealed against hose-down. Suitable for indoor panel mounting; not for washdown zones without an additional enclosure.

Auxiliary contacts and release options

MPN
3VA1116-5EE32-0AG0