Skip to main content
Siemens 3VA1116-5EE32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-5EE32-0CH0 MCCB, 160A, 187kA @240V

MPN3VA1116-5EE32-0CH0

Siemens SENTRON 3VA, molded case circuit breaker, 3-pole, 160 A, 187 kA breaking capacity at 240 V AC, line protection, undervoltage release, 2 aux + 1 trip alarm switch, DIN-rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-5EE32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11165EE320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1116-5EE32-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.40.5 W

Protection & Trip Unit

3VA1116-5EE32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1116-5EE32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-5EE32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1116-5EE32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-5EE32-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1116-5EE32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for continuous 160 A at 40 °C, with a massive 187 kA interrupting capacity at 240 V AC — that's the headline number for fault-current duty on a low-voltage distribution board. At 415 V it still breaks 121 kA, and at 440 V it holds 75.6 kA, so it handles high-fault scenarios common in industrial mains without cascading upstream.

Line protection and auxiliary fit

Designed for line protection — meaning it sits on the feeder, not a motor circuit. The unit ships with an undervoltage release (UVR) pre-installed, so it drops out on a sag below the release threshold. Auxiliary switching comes as 2 auxiliary switches plus 1 trip alarm switch HQ, enough for status feedback to a PLC or remote I/O. Rated insulation voltage is 800 V, and the operating temperature span runs from -25 °C to +70 °C, with storage down to -40 °C. The 40.5 W max power loss at full load matters for enclosure thermal budgeting — factor it into your panel heat calculation.

Panel integration

Mounts on a standard DIN rail. Footprint is 70 mm deep, 76.2 mm wide, 130 mm tall — three poles in a 76.2 mm width is a compact fit for a 160 A MCCB. The 70 mm depth stays inside a 200 mm enclosure depth, leaving room for cables and busbars behind the door.

Frequently asked questions

Where can I buy 3VA1116-5EE32-0CH0 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

What is the breaking capacity at 240 V?

187 kA at 240 V AC, with 121 kA at 415 V and 75.6 kA at 440 V — sufficient for most industrial high-fault applications.

Does this MCCB include an undervoltage release?

Yes, an undervoltage release (UVR) is fitted as standard on this variant.

What is the continuous current rating at elevated ambient?

Rated 160 A continuous up to 50 °C, then derates to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C.

MPN
3VA1116-5EE32-0CH0