The interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — so it handles high-fault panels without cascading upstream. The 3-pole frame and IP40 front protection make it a straightforward fit for a standard distribution board or motor control center.
Thermal derating — what 160 A really means at panel temperature
At 55 °C it derates to 153.6 A, at 60 °C to 150.4 A, at 65 °C to 147.2 A, and at 70 °C to 144 A.
Auxiliary contacts and release options
The TM240 release is fixed, not adjustable for short-time delay.