Siemens 3VA1116-5EF32-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-5EF32-0HH0 SENTRON MCCB, 160 A, 187 kA at 24

MPN3VA1116-5EF32-0HH0

Siemens SENTRON 3VA1116-5EF32-0HH0, molded case circuit breaker, 3-pole, 160 A, 187 kA at 240 V, TM240 overcurrent release, shunt trip, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-5EF32-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1116-5EF32-0HH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1116-5EF32-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1116-5EF32-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-5EF32-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1116-5EF32-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-5EF32-0HH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Line protection MCCB with 187 kA interrupting capacity

The Siemens SENTRON 3VA1116-5EF32-0HH0 is a 3-pole molded case circuit breaker rated for line protection, carrying a continuous current Iu of 160 A and an interrupting capacity of 187 kA at 240 V. That 187 kA figure at 240 V is the headline number for panel SCCR calculations — it tells you this breaker can safely interrupt a fault up to that level without cascading upstream. At 415 V it still holds 121 kA, and at 690 V it drops to 17 kA, which is typical for a compact-frame MCCB at higher voltage. The TM240 thermal-magnetic overcurrent release handles the overload and short-circuit protection curve; the shunt trip (STL) allows remote tripping via a control signal. It ships with 2 auxiliary switches plus a separate trip alarm switch (HQ) for status feedback to a PLC or annunciator.

Thermal derating and panel fit

The 160 A rating holds flat from 40 °C through 50 °C — no derating needed in a typical 40 °C panel. Above that it steps down: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. If your enclosure runs hot, use the 60 °C figure for conservative sizing. The breaker measures 130 mm high by 76.2 mm wide by 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount backplates. IP40 on the front face means it's protected against solid objects over 1 mm but not sealed against water ingress; keep it inside a rated enclosure for washdown areas.

Frequently asked questions

What is the interrupting capacity of 3VA1116-5EF32-0HH0 at different voltages?

The breaker is rated 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. Use the 240 V figure for panel SCCR calculations; the 415 V figure governs most European industrial installations.

What is the continuous current rating and how does it derate with temperature?

Rated continuous current Iu is 160 A, holding flat from 40 °C to 50 °C. It derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C.

What auxiliary contacts and trip accessories come with this breaker?

It includes 2 auxiliary switches plus 1 trip alarm switch (HQ configuration). The integrated shunt trip (STL) allows remote tripping. The auxiliary trip accessory order code is 3VA9688-0BL30.

Where can I buy 3VA1116-5EF32-0HH0 and how is it quoted?

We source this breaker through independent distribution channels and quote it to order against an RFQ. Availability and current pricing are confirmed at quote time.

MPN
3VA1116-5EF32-0HH0