Trip settings and accessories
Overload protection (Ir) is adjustable from 112 A to 160 A via the ATAM dial; short-circuit protection (Ii) is fixed at 5 to 10 times In, so a 160 A breaker trips magnetically between 800 A and 1600 A. The built-in undervoltage release (UVR) operates on 120–127 V AC, 50/60 Hz — common for North American control voltages stepped down from a 480 V panel.
