The 3VA1116-5EF36-0JC0: The 160 A continuous rating holds flat from 40 °C to 50 °C, then derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. The 15 000-cycle mechanical endurance (latching) is typical for this class; it is not a high-cycle motor-starting breaker.

Siemens 3VA1116-5EF36-0JC0 SENTRON MCCB, 160 A, 3-pole, 187
Siemens SENTRON 3VA1116-5EF36-0JC0, molded case circuit breaker, 3-pole, 160 A, 187 kA at 240 V, line protection, TM240 overcurrent release, shunt trip, IP40 front.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Line protection |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AA12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Current at 40 °C | 160 A |
| Current at 45 °C | 160 A |
| Current at 50 °C | 160 A |
| Current at 55 °C | 153.6 A |
| Current at 60 °C | 150.4 A |
| Current at 65 °C | 147.2 A |
| Current at 70 °C | 144 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 75.6 kA |
| Breaking capacity at 690 V | 17 kA |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM240 |
| Parameter | Value |
|---|---|
| Main circuit connection type | box terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |
Product details
Frequently asked questions
How do I get current pricing and availability for 3VA1116-5EF36-0JC0?
Submit an RFQ through the storefront; pricing and stock are confirmed at quote time through independent distribution channels.
What is the interrupting capacity of 3VA1116-5EF36-0JC0 at 415 V?
121 kA at 415 V, which is the typical line-to-line voltage for European industrial panels and provides substantial selectivity headroom.
Does 3VA1116-5EF36-0JC0 include a shunt trip?
Yes, it is fitted with a shunt trip (STL) auxiliary release, plus two HQ auxiliary switches.