Skip to main content
Siemens 3VA1116-5EF42-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-5EF42-0AH0 Circuit Breaker, 160A, 55kA @ 415

MPN3VA1116-5EF42-0AH0

Siemens 3VA1 series, IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 4-pole, line protection TM240, In=160A, overload Ir=112A...160A, short-circuit Ii=5...10 x In, N conductor unprotected, nut keeper kit, 2 auxiliary switches HQ, 1 trip alarm switch HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

What this breaker is and what the ratings mean

The Siemens 3VA1116-5EF42-0AH0 is a 4-pole IEC frame 160 molded-case circuit breaker with breaking capacity class M, rated Icu = 55 kA at 415 V AC. That interrupting rating means it can safely clear a fault up to 55 kA without rupturing — sufficient for most industrial secondary-distribution switchboards where the prospective short-circuit current sits in that range. The TM240 thermal-magnetic trip unit gives overload protection adjustable from 112 A to 160 A (Ir), and short-circuit pickup (Ii) adjustable 5 to 10 times the rated continuous current In = 160 A. For a panel builder, this means you set Ir to match the cable or busway ampacity, and Ii to coordinate with downstream breakers — typically 5x for general loads, 10x for motor circuits with higher inrush.

Deployment context and integration

This breaker mounts on a DIN rail or directly onto a mounting plate inside an enclosure. The nut keeper kit holds the line and load lug nuts captive during wiring — a time-saver when you're landing 160 A cables in a tight gland plate. The N conductor is unprotected (solid neutral), so this is a 3-pole + N configuration; the neutral bar passes through without overcurrent protection. Two auxiliary switches (HQ) and one trip alarm switch (HQ) are factory-fitted, giving remote status for PLC or SCADA inputs without additional wiring modules.

Frequently asked questions

Where can I buy 3VA1116-5EF42-0AH0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm availability and current pricing.

What is the breaking capacity of this breaker?

The breaking capacity class M gives Icu = 55 kA at 415 V AC, suitable for high-fault-current secondary distribution.

What overload protection range does the TM240 trip unit provide?

The TM240 thermal-magnetic trip unit allows overload protection adjustable from 112 A to 160 A (Ir), with short-circuit pickup adjustable 5 to 10 times In (160 A).

MPN