Skip to main content
Siemens 3VA1116-5GE42-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-5GE42-0AF0 SENTRON MCCB, 160 A, 4-Pole, 187

MPN3VA1116-5GE42-0AF0

Siemens SENTRON 3VA1116-5GE42-0AF0, molded case circuit breaker, 160 A, 4-pole, line protection, TM220 release, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-5GE42-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11165GE420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1116-5GE42-0AF0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.38 W

Protection & Trip Unit

3VA1116-5GE42-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1116-5GE42-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-5GE42-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1116-5GE42-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-5GE42-0AF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1116-5GE42-0AF0 is a 160 A, 4-pole molded case circuit breaker (MCCB) designed for line protection. It carries a TM220 thermal-magnetic release, meaning it handles overloads thermally and short-circuits magnetically — the standard for feeder and distribution protection in commercial and industrial panels. The interrupting ratings are substantial: 187 kA at 240 V AC, 121 kA at 415 V AC, and 75.6 kA at 440 V AC, with a rated insulation voltage of 800 V. This is a high-interrupting-capacity frame for high-fault locations like substation mains or large switchboards.

Interrupting capacity and thermal derating

At 500 V and 690 V the interrupting rating drops to 17 kA — still adequate for most 480/600 V class distribution, but worth checking if your fault current exceeds that at the higher voltage. The breaker is rated 160 A continuously up to 50 °C ambient; above that it derates to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. If your panel runs hot, the 160 A frame may need to be applied at 150 A or lower to avoid nuisance tripping.

Physical fit and auxiliary options

The breaker measures 130 mm high, 101.6 mm wide, and 70 mm deep — a standard 4-pole MCCB footprint that mounts directly on a DIN rail or panel plate. It ships with one auxiliary switch and one trip alarm switch (HQ type), so you get remote status indication without ordering a separate accessory. There is no undervoltage release, no ground-fault monitoring, and no communication function built in; those are add-on modules if needed.

Frequently asked questions

What is 3VA1116-5GE42-0AF0's listed depth?

The depth is 70 mm (2.76 in), with a width of 101.6 mm (4 in) and height of 130 mm (5.12 in).

MPN