Skip to main content
Siemens 3VA1116-6EE32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-6EE32-0AB0 SENTRON MCCB, 160 A, 3-Pole, 220

MPN3VA1116-6EE32-0AB0

Siemens SENTRON 3VA1116-6EE32-0AB0, molded case circuit breaker, 3-pole, 160 A, TM220 thermal-magnetic release, 220 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-6EE32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11166EE320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA1116-6EE32-0AB0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.38 W
3VA1116-6EE32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1116-6EE32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-6EE32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1116-6EE32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-6EE32-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens 3VA1116-6EE32-0AB0 is a SENTRON molded case circuit breaker rated 160 A continuous at 40 °C, with a TM220 thermal-magnetic release and 3-pole construction. Its interrupting capacity reaches 220 kA at 240 V, 154 kA at 415 V, and 75.6 kA at 440 V — figures that cover most industrial service-entrance and feeder applications where high fault current is expected.

Thermal-magnetic curve and derating

The TM220 release is a fixed thermal-magnetic overcurrent trip. At 40 °C the breaker carries 160 A; at 55 °C it derates to 158 A, and at 70 °C to 150 A (–). Max power loss is 38 W — a figure to account for in enclosure heat calculations.

Frequently asked questions

What is the interrupting capacity of 3VA1116-6EE32-0AB0 at 240 V?

The interrupting capacity is 220 kA at 240 V. At 415 V it is 154 kA, at 440 V it is 75.6 kA, and at 500 V and 690 V it is 17 kA (–).

Where can I buy 3VA1116-6EE32-0AB0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA1116-6EE32-0AB0