Siemens 3VA1116-6EF32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-6EF32-0DA0 SENTRON MCCB, 160A, 3-Pole, 220kA

MPN3VA1116-6EF32-0DA0

Siemens SENTRON 3VA1116-6EF32-0DA0, molded case circuit breaker, 3-pole, 160 A rated current, TM240 thermal-magnetic overcurrent release, with undervoltage release, 220 kA breaking capacity at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-6EF32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11166EF320AA0
3VA1116-6EF32-0DA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.40.5 W
3VA1116-6EF32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1116-6EF32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-6EF32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1116-6EF32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-6EF32-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Line protection MCCB with TM240 release and undervoltage release

The Siemens SENTRON 3VA1116-6EF32-0DA0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current at 40 °C, designed for line protection per the product designation. It carries a TM240 thermal-magnetic overcurrent release — the thermal element handles overloads, the magnetic element handles short-circuits, with the trip threshold set at 240 A (1.5× the continuous rating).

Breaking capacity varies with system voltage: 220 kA at 240 V AC, 154 kA at 415 V AC, 75.6 kA at 440 V AC, and 17 kA at both 500 V and 690 V AC. At 240 V this is a high-interrupting rating suitable for transformer secondary or large bus feeds where fault current is substantial.

Continuous current holds at 160 A from 40 °C through 50 °C ambient. Above that, derating applies: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. The operating ambient range is -25 °C to +70 °C; storage range is -40 °C to +80 °C.

Dimensions: 130 mm height, 76.2 mm width (3 inches), 70 mm depth. The 3-inch width is standard for a 3-pole MCCB in this frame size — it occupies one 3-pole mounting position on a DIN rail or panel-mount adapter. Rated insulation voltage is 800 V, which covers 480/277 V and 600 V systems with margin.

This is an active catalog item in the Siemens SENTRON 3VA platform.

Frequently asked questions

Where can I buy 3VA1116-6EF32-0DA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not before.

What is the breaking capacity of 3VA1116-6EF32-0DA0 at 240 V?

220 kA at 240 V AC. At 415 V it is 154 kA, at 440 V it is 75.6 kA, and at 500 V and 690 V it is 17 kA.

Does 3VA1116-6EF32-0DA0 include an undervoltage release?

Yes, it includes a factory-installed undervoltage release (UVR) as the auxiliary release type, which trips the breaker when control voltage drops below the dropout threshold.

MPN
3VA1116-6EF32-0DA0