Siemens 3VA1116-6EF32-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-6EF32-0HH0 SENTRON MCCB, 160 A, 3-Pole, 220

MPN3VA1116-6EF32-0HH0

Siemens SENTRON 3VA1116-6EF32-0HH0, molded case circuit breaker, 160 A, 3-pole, 220 kA at 240 V, TM240 overcurrent release, shunt trip, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-6EF32-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1116-6EF32-0HH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1116-6EF32-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1116-6EF32-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-6EF32-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1116-6EF32-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-6EF32-0HH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1116-6EF32-0HH0 is a 3-pole molded case circuit breaker rated for line protection, carrying a continuous current Iu of 160 A and an insulation voltage Ui of 800 V. Its interrupting capacity hits 220 kA at 240 V, 154 kA at 415 V, and 75.6 kA at 440 V — numbers that matter when coordinating downstream faults on a high-fault panel feed.

Thermal-magnetic curve and temperature derating

The overcurrent release is a TM240 — thermal-magnetic, fixed, 240 A frame, set at the factory to the 160 A rating. The breaker holds 160 A flat from 40 °C through 50 °C, then derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. If your panel ambient runs above 50 °C, the real-world continuous current is lower than the nameplate Iu.

Auxiliaries and trip options

Factory-fitted with 2 auxiliary switches plus 1 trip alarm switch (HQ type), and a shunt trip release (STL) for remote tripping. No undervoltage release, no ground-fault monitoring, no phase-failure detection, no communication module — this is a pure line-protection breaker, not a power-monitoring device. The integrated auxiliary trip order code is 3VA9688-0BL30 if you need a spare or replacement.

Mounting and environment

Dimensions: 130 mm high, 76.2 mm wide, 70 mm deep. Front protection IP40 — suitable for enclosed panel mounting where no water jets or dust ingress are expected. Operating temperature range -25 °C to 70 °C; storage from -40 °C to 80 °C. Mechanical endurance rated at 15 000 cycles.

Frequently asked questions

How do I get current pricing and availability for 3VA1116-6EF32-0HH0?

This part is sourced to order against an RFQ through independent distribution. Submit the order code with your target quantity; we confirm pricing and lead time at quote time.

What is the interrupting capacity of 3VA1116-6EF32-0HH0 at different voltages?

220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. The highest rating is at 240 V; the capacity drops as voltage rises.

Does 3VA1116-6EF32-0HH0 include a shunt trip or undervoltage release?

It includes a shunt trip release (STL) for remote tripping, but no undervoltage release. Auxiliaries are 2 switches plus 1 trip alarm (HQ).

MPN
3VA1116-6EF32-0HH0