It delivers 220 kA breaking capacity at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — numbers that govern selectivity and SCCR coordination in the distribution panel.
Lifecycle stage is current production, so this is a standard BOM line — no last-time-buy scramble, no surplus-channel premium.
Panel integration is straightforward: 76.2 mm wide (roughly 3 inches on a DIN pitch), 130 mm tall, 70 mm deep. The TM240 release is adjustable; tr max. is 1 s at the listed current, which matters for coordination with downstream feeders.