Skip to main content
Siemens 3VA1116-6EF36-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-6EF36-0BA0 SENTRON MCCB, 160 A, 3-Pole, 220

MPN3VA1116-6EF36-0BA0

Siemens SENTRON 3VA1116-6EF36-0BA0, molded case circuit breaker, 3-pole, 160 A at 40 °C, 220 kA breaking capacity at 240 V, line protection, with undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-6EF36-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11166EF360AA0

Ratings

3VA1116-6EF36-0BA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.40.5 W

Protection & Trip Unit

3VA1116-6EF36-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1116-6EF36-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-6EF36-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1116-6EF36-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-6EF36-0BA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

SENTRON 3VA1116-6EF36-0BA0 — 160 A MCCB with UVR, current production

The Siemens SENTRON 3VA1116-6EF36-0BA0 is a 3-pole molded case circuit breaker rated 160 A at 40 °C, designed for line protection in distribution panels. Breaking capacity hits 220 kA at 240 V — enough for high-fault utility feeds or transformer secondaries where SCCR headroom matters. An undervoltage release (UVR) is built in, so it drops the load on loss of control voltage without a separate shunt trip module. Rated insulation voltage is 800 V, and the thermal-magnetic trip unit is the TM240 type — fixed thermal, fixed magnetic, no adjustment. Power loss maxes at 40.5 W, which matters for enclosure heat rise if you're packing several breakers in a small panel.

Breaking capacity across voltage — selectivity planning

The 3VA1116-6EF36-0BA0 delivers 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. That 17 kA floor at 690 V is the limiting figure for coordination studies — if your upstream transformer can push more fault current at that voltage, you need a current-limiting upstream device or a larger-frame breaker. Thermal derating starts at 55 °C: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, 150 A at 70 °C. Operating range is -25 °C to 70 °C ambient; storage from -40 °C to 80 °C. For a 160 A continuous load, keep ambient below 50 °C to avoid nuisance tripping.

Panel fit — dimensions and mounting

Width 76.2 mm (3 in), depth 70 mm (2.76 in), height 130 mm (5.12 in). Three-pole footprint matches the standard SENTRON 3VA mounting plate pattern — no adapter needed for existing 3VA panel layouts. No communication function, no ground-fault monitoring, no trip indicator on this variant.

Frequently asked questions

What is the breaking capacity of 3VA1116-6EF36-0BA0 at 240 V?

220 kA at 240 V. At 415 V it is 154 kA, at 440 V it is 75.6 kA, and at 500 V or 690 V it is 17 kA.

What is the rated current of this MCCB at elevated ambient temperatures?

Rated 160 A from 40 °C to 50 °C. Derates to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C.

Does 3VA1116-6EF36-0BA0 include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) as the auxiliary release. No separate shunt trip module is needed for undervoltage protection.

Where can I buy 3VA1116-6EF36-0BA0 and how is it quoted?

Sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not listed here.

MPN
3VA1116-6EF36-0BA0