Skip to main content
Siemens 3VA1116-6EF36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-6EF36-0JA0 SENTRON MCCB, 160 A, 3-Pole, 220

MPN3VA1116-6EF36-0JA0

Siemens SENTRON 3VA1116-6EF36-0JA0, molded case circuit breaker, 3-pole, 160 A rated continuous current, TM240 overcurrent release, line protection, 220 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-6EF36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1116-6EF36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1116-6EF36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1116-6EF36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-6EF36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1116-6EF36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-6EF36-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens SENTRON 3VA1116-6EF36-0JA0 — 160 A MCCB with TM240 Release

Its TM240 thermal-magnetic overcurrent release provides fixed trip curves for overload and short-circuit protection without the need for external trip units. The interrupting capacity reaches 220 kA at 240 V, 154 kA at 415 V, and 75.6 kA at 440 V — figures that govern its suitability for high-fault installations like transformer secondaries or large motor control centers.

The 160 A rating holds flat from 40 °C through 50 °C, then derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. Plan your load margin accordingly. No interchangeable trip units, no field-adjustable long-time or short-time pickup. That simplifies ordering and reduces the chance of mis-configuration, but it also means the breaker is dedicated to its 160 A frame. If your load changes, you swap the whole MCCB, not just the trip. The shunt trip (STL) auxiliary release is built in — order code 3VA9688-0BL32 for the integrated auxiliary trip. No undervoltage release, no ground fault monitoring, no phase failure detection. If you need remote tripping via a PLC or E-stop circuit, the shunt trip covers that; if you need undervoltage protection, you add an external UVR module.

Frequently asked questions

Will 3VA1116-6EF36-0JA0 drop into a panel specified around 3VA1110-5EE32-0JA0?

Yes, the 70 mm depth and 76.2 mm width are identical across the 3VA111x frame, so it fits the same busbar system and DIN-rail mounting without rewiring the panel layout.

MPN