Siemens 3VA1116-6EF36-0JH0 SENTRON MCCB, 160 A, 220 kA at 24

MPN3VA1116-6EF36-0JH0

Siemens SENTRON 3VA1116-6EF36-0JH0, 3-pole molded case circuit breaker, 160 A rated continuous current (Iu), TM240 thermal-magnetic release, 220 kA interrupting at 240 V, shunt trip (STL), IP40 front, 70 x 76.2 x 130 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1116-6EF36-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1116-6EF36-0JH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1116-6EF36-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1116-6EF36-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1116-6EF36-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1116-6EF36-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1116-6EF36-0JH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

SENTRON 3VA1116-6EF36-0JH0 — 160 A MCCB, line protection, shunt trip

The Siemens 3VA1116-6EF36-0JH0 is a SENTRON 3-pole molded case circuit breaker rated for 160 A continuous current (Iu) with a TM240 thermal-magnetic overcurrent release. It is configured for line protection — no ground-fault monitoring, no phase-failure detection, no communication module. The interrupting ratings climb to 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V, which covers most industrial distribution panels and motor control center feeder positions. A shunt trip (STL) auxiliary release is factory-installed, and the auxiliary contact block provides 2 auxiliary switches plus 1 trip alarm switch (HQ). The TM240 release is a fixed thermal-magnetic unit — no interchangeable rating plugs. The breaker carries an IP40 rating on the front face, sufficient for general-purpose panel mounting where drip shields or higher ingress protection are not required.

Current derating and thermal limits

The 160 A rating holds flat from 40 °C through 50 °C ambient. Above that, the breaker derates: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. The operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. If the panel ambient runs above 50 °C, the continuous current capability drops by about 6 A per 5 °C step — factor that into the feeder sizing.

Panel fit and dimensions

Dimensions: 70 mm deep, 76.2 mm wide, 130 mm tall. The 3-pole footprint matches the standard 3VA111x frame width. The breaker mounts via screw-clamp terminals on the line and load sides — no DIN-rail clip. The shunt trip (STL) and auxiliary contact block are integrated into the breaker body, so the overall depth stays at 70 mm including the accessory stack. The IP40 front face is suitable for enclosed panel mounting; no additional gasketing needed for standard indoor environments.

Frequently asked questions

Where can I buy 3VA1116-6EF36-0JH0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting rating of 3VA1116-6EF36-0JH0 at 240 V?

220 kA at 240 V. The breaker also carries 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V.

What auxiliary contacts does this MCCB include?

It comes with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration), and a factory-installed shunt trip (STL) release.

Does 3VA1116-6EF36-0JH0 include ground fault or phase failure protection?

No. This variant is configured for line protection only — no ground fault monitoring, no phase failure detection, and no communication function.

MPN