SENTRON 3VA1116-6EF36-0JH0 — 160 A MCCB, line protection, shunt trip
It is configured for line protection — no ground-fault monitoring, no phase-failure detection, no communication module. The interrupting ratings climb to 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V, which covers most industrial distribution panels and motor control center feeder positions. The breaker carries an IP40 rating on the front face, sufficient for general-purpose panel mounting where drip shields or higher ingress protection are not required.
Above that, the breaker derates: 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C.
The 3-pole footprint matches the standard 3VA111x frame width. The breaker mounts via screw-clamp terminals on the line and load sides — no DIN-rail clip. The shunt trip (STL) and auxiliary contact block are integrated into the breaker body, so the overall depth stays at 70 mm including the accessory stack. The IP40 front face is suitable for enclosed panel mounting; no additional gasketing needed for standard indoor environments.