Breaking capacity is 220 kA at 240 V AC, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V — these figures cover most industrial low-voltage networks and give solid selectivity headroom downstream. The 160 A rating holds at ambient temperatures up to 50 °C; above that it derates to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. If the panel runs hot — near a transformer or in a non-climate-controlled enclosure — check the actual load against the derated value rather than the nameplate 160 A.
Physical fit and integration
No undervoltage release, no trip indicator, no communication function, and no ground-fault monitoring are included on this variant.