Skip to main content
Siemens 3VA1116-6GF46-0KF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-6GF46-0KF0 SENTRON MCCB, 160 A, 70 kA @ 415

MPN3VA1116-6GF46-0KF0

Siemens SENTRON 3VA1 series, molded case circuit breaker, 160 A frame, breaking capacity class H, 70 kA @ 415 V, 4-pole, line protection, TM240 thermal-magnetic release, shunt trip (STL), 1 auxiliary switch HQ + 1 trip alarm switch HQ, front terminal.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-6GF46-0KF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1116-6GF46-0KF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1116-6GF46-0KF0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-6GF46-0KF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Auxiliary CO contacts2
3VA1116-6GF46-0KF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Product details

MCCB for line protection with integrated shunt trip

The TM240 release provides LI protection — thermal overload (Ir adjustable 112–160 A) and magnetic short-circuit (Ii adjustable 5–10 × In) — sized for feeder or main distribution duty in commercial and industrial switchboards. The 4-pole design with 100% N-conductor protection means the neutral pole is fully rated and switched — required where harmonic currents or unbalanced loads demand a protected neutral path. The auxiliary contact pack — one HQ auxiliary switch plus one HQ trip alarm switch (order code 3VA9988-0AB12) — provides status feedback for remote indication and monitoring.

Mounting and connection

Front-terminal connection on the main current circuit accepts lug-type conductors, typical for panel-mounted MCCBs where busbar or cable access is from the front. The 15 000-cycle mechanical endurance is standard for a distribution-class MCCB in non-frequent switching service.

Frequently asked questions

What are the key ratings of the 3VA1116-6GF46-0KF0?

160 A frame size, breaking capacity class H at 70 kA / 415 V AC, 4-pole with 100% N-conductor protection, TM240 thermal-magnetic release (Ir 112–160 A, Ii 5–10 × In), shunt trip (STL) for remote tripping, and one HQ auxiliary switch plus one HQ trip alarm switch.

Where can I buy the 3VA1116-6GF46-0KF0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What compliance documentation does Siemens provide for this MCCB?

As a SENTRON 3VA1 series device, it is designed to IEC 60947-2 and carries CE marking for the European market. RoHS and REACH declarations are standard from Siemens. For specific UL or marine classification documentation, verify the exact variant against the manufacturer's compliance matrix at time of order.

MPN
3VA1116-6GF46-0KF0