Skip to main content
Siemens 3VA1120-3EF32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-3EF32-0AH0 SENTRON MCCB, 20 A, 3-Pole, Line

MPN3VA1120-3EF32-0AH0

Siemens SENTRON 3VA1120-3EF32-0AH0, 3-pole molded case circuit breaker, 20 A rated continuous current, TM240 thermal-magnetic release, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1120-3EF32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1120-3EF32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C19.2 A
Current at 60 °C18.8 A
Current at 65 °C18.4 A
Current at 70 °C18 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1120-3EF32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1120-3EF32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1120-3EF32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1120-3EF32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1120-3EF32-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

This is a straightforward, fixed-trip breaker for standard branch-circuit protection in distribution panels.

Breaking capacity — what it clears and where

This MCCB delivers 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. At 415 V, the 52.5 kA figure gives comfortable headroom above typical 25–36 kA utility fault levels in most industrial panels. At 690 V, the 10.5 kA rating is lower but still covers many motor-control center applications.

At 55 °C it derates to 19.2 A; at 60 °C to 18.8 A; at 65 °C to 18.4 A; at 70 °C to 18 A. Above that, the continuous load must be reduced accordingly. The TM240 release has a maximum adjustable time setting of 1 second for the long-time delay.

Physical fit and auxiliary contacts

Footprint is 76.2 mm wide, 130 mm high, 70 mm deep — standard 3-pole MCCB width for DIN-rail or screw-mount panel integration.

Frequently asked questions

Where can I buy 3VA1120-3EF32-0AH0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1120-3EF32-0AH0 at different voltages?

It interrupts 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V.

Does 3VA1120-3EF32-0AH0 have auxiliary contacts?

Yes, it comes with 2 auxiliary switches plus 1 trip alarm switch (HQ type).

MPN
3VA1120-3EF32-0AH0