Skip to main content
Siemens 3VA1120-3EF32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-3EF32-0KA0 Circuit Breaker, 20A, 25kA @ 415V

MPN3VA1120-3EF32-0KA0

Siemens 3VA1 IEC frame 160, 3-pole circuit breaker, breaking capacity class N, Icu=25kA @ 415V, line protection TM240, ATAM, In=20A, overload Ir=14A...20A, short-circuit Ii=8...16 x In, shunt trip (STL) 220-250V DC, 208-277V AC, nut keeper kit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

The 3VA1120-3EF32-0KA0 is a Siemens 3VA1 IEC frame 160 molded-case circuit breaker, 3-pole, with a breaking capacity class N rating of Icu=25kA at 415 V AC. The thermal-magnetic trip unit is a TM240, meaning the fixed thermal element is sized for a 20 A continuous current (In), with an adjustable overload protection range (Ir) from 14 A to 20 A, and a short-circuit magnetic pickup (Ii) adjustable from 8 to 16 times In — so from 160 A to 320 A. This lets you tune the overload band to the actual load current without swapping the breaker body.

Deployment context

The integrated shunt trip (STL) operates on 220–250 V DC or 208–277 V AC, allowing remote tripping from an emergency-stop circuit or a PLC digital output. The nut keeper kit secures the line/load lug connections — a detail that matters during panel wiring when you're torquing multiple breakers on the same bus.

Frequently asked questions

How do I get current pricing and availability for 3VA1120-3EF32-0KA0?

Pricing and availability are confirmed at quote time against an RFQ through independent distribution. Submit an RFQ for a current quote and lead-time estimate.

What is the breaking capacity and protection range of this breaker?

The 3VA1120-3EF32-0KA0 has a breaking capacity Icu=25kA at 415 V AC, an adjustable overload protection Ir from 14 A to 20 A, and a short-circuit magnetic pickup Ii adjustable from 8 to 16 times In (160 A to 320 A).

What voltage does the shunt trip operate on?

The integrated shunt trip (STL) operates on 220–250 V DC or 208–277 V AC.

MPN
3VA1120-3EF32-0KA0