Skip to main content
Siemens 3VA1120-3EF36-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-3EF36-0HA0 SENTRON MCCB, 20 A, 75.6 kA at 24

MPN3VA1120-3EF36-0HA0

Siemens SENTRON 3VA1120-3EF36-0HA0, molded case circuit breaker, 3-pole, line protection, TM240 thermal-magnetic release, 20 A rated at 40 °C, 75.6 kA at 240 VAC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1120-3EF36-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11203EF360AA0
3VA1120-3EF36-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.12 W
3VA1120-3EF36-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1120-3EF36-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1120-3EF36-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1120-3EF36-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1120-3EF36-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Integrator note — 3VA1120-3EF36-0HA0

Rated 20 A continuously at ambient temperatures from 40 °C through 55 °C, derating to 19 A at 60–70 °C — so in a warm panel near the top of the enclosure, plan for the 19 A ceiling rather than the 20 A nameplate. Breaking capacity is 75.6 kA at 240 VAC, 52.5 kA at 415 VAC, and 32 kA at 440 VAC — figures that govern fault-current withstand for the downstream distribution; at 500 V and 690 V it holds 11.9 kA.

Width 76.2 mm (3 in), depth 70 mm (2.76 in), height 130 mm (5.12 in) — fits standard SENTRON 3VA mounting footprints; verify bus-bar and lug spacing against the existing panel layout before committing the BOM line.

Frequently asked questions

Does 3VA1120-3EF36-0HA0 include a shunt trip?

Yes, it includes a shunt trip (STL) auxiliary release for remote tripping.

MPN
3VA1120-3EF36-0HA0